6 Setup

VEGATOR 112 •

46106-EN-131217

Yellow

– Relay control lamp

– The yellow relay control lamp reacts depending on the set

mode

– The relay control lamp generally indicates the activated (ener-

gized) condition of the relay

– A dark relay control lamp means that the relay is deenergised

The DIL switch block is located behind the front cover. The individual

switches are assigned as follows:

3
4
5

max

min

1
2

max

min

CH

1

CH

2

Fig. 3: DIL switch VEGATOR 112
1 Mode (min./max. adjustment), channel 1

2 Line monitoring Off/On, channel 1

3 Mode (min./max. adjustment), channel 2

4 Line monitoring Off/On, channel 2

5 Two-point control On/Off

The requested operating mode is set with the min./max. switch (min.

detection i.e. dry run protection or max. detection i.e. overfill protec-

tion)

Dry run protection: Relay is switched off when the level falls

below the min. level (safe currentless state), relay is switched on

again when the max. level is exceeded (switch-on point > switch-

off point)

Overflow protection: Relay is switched off when the max. level is

exceeded (safe currentless state), relay is switched on again when

the level falls below the min. level (switch-on point < switch-off

point)

Note:

The mode selection on the signal conditioning instrument only func-

tions correctly if the mode switch on the sensor is set to "Max.".

As opposed to simple level detection, two-point control allows the

switch-on and switch-off points to be set at different locations (hys-

teresis). This hysteresis can be defined via the mounting positions,

i.e. the distance between the two sensors. The principle is used, for

example, to control pumps for filling and emptying. Thus, for example,

the filling of a vessel can be switched on at 10 % level and switched

off again at 90 % level. The two output relays behave identically in this

mode.

When NAMUR level switches are connected, the line monitoring func-

tion can check the input continuously for line break or short-circuit. If

DIL switch block

Mode (min./max. adjust-

ment)

Two-point control

Line monitoring