Technical Data

FN-LB-I

098

91

8_

EN

G.xm

l

2

003

-03-

2

4

Supply

Rated voltage

≤ 48 V

Rated current

≤ 250 mA

Leakage current

≤ 5 µA

On-state voltage

≤ 85 V

Ground insulation

≥ 500 V breakdown voltage

Ambient conditions

Ambient temperature

-30 ... 60 °C (243 ... 333 K) for Ex application; please observe declaration of conformity

Mechanical specifications

Housing material

stainless steel 1.4401 (AISI 316)
surface all over polished

Protection degree

IP20

Data for application in conjunction
with hazardous areas

EC-Type Examination Certificate

PTB 00 ATEX 2175 , conformity information is to consider

Group, category, type of protection,
Temperature classification

¬ II 2 G EEx ia IIC T6

Voltage U

i

50 V

Type of protection [EEx ia and EEx ib]

Internal capacitance (EEx ia)

negligibly small

Internal inductance (EEx ia)

negligibly small

Nominal leakage current

10 kA (8/20

µs) per core according to IEC 60-2

Nominal response time

Symmetrical

1 ns

Asymmetric

100 ns

Bandwidth

≥ 40 kHz

Surge protectors must always be connected to a solid ground (large cross sections, short wiring). This is the basic requirement
for an effective protection.

Examples:

Notes

Length 400 mm
Cross sectional area 1.0 mm

M20 x 1.5 or
PG13.5 or ½" NPT

22

22

55

Terminal box

Transmitter

GND

F*-LB-I