SAFETY

Location of module

Safe area, Zone 2, IIC T4 hazardous area or Class 1, Div 2,
Groups A, B, C, D T4 hazardous location.

Location of field wiring

Zone 1, IIC T4 hazardous area or Class 1, Div 1, Groups A, B,C,
D T4 hazardous location.

Field wiring protection

Intrinsically safe

Certification Code

II(2) GD [EEx ib] IIC, II 3 GD EEx nA IIC T4.

Safety description

14V, 180mA, 2.52W, 0.20

µF*, 300µH*

FM entity parameters

14V, 180mA, 2.52W, 0.20

µF*, 300µH*

ATEX certificate numbers

MTL02ATEX9121
BAS02ATEX7276

FM certificate number

J.I.3012571

Certification is compatible with

Fieldbus FOUNDATION FF816-FISCO.
IEC/TS 60079-27 FISCO Technical Specification.

MECHANICAL

Mounting

DIN rail/surface mounting

Module width

42mm

Weight

360g

LED INDICATORS

OFF

ON

Power (green)

Power fail

Power OK

Fault (red)

Normal

Fault

Host Comm (yellow)

Comms failure

Comms OK

IS Comm (yellow)

Comms failure

Comms OK

Typically more than 6 IS fieldbus

devices per power supply

Fieldbus repeater

Multidrop isolators on single fieldbus link

Power, fault and repeater LEDs

250V ac input/output/power supply

isolation

Switch selectable terminator on host side

Fixed terminator on IS side

Switch selectable power for host side

Mountable in Zone/Division 2

MODULE SPECIFICATION

See also System Specification

OUTPUT

Number of channels

One

Voltage

12.0V (min.) at 0°C (see note)

Design Current

0 to 120mA

Output ripple

Complies with clause 22.6.2 of the fieldbus standard†

Minimum load

No load

Maximum cable length

Determined by IS load, see Application Note AN9026 for details

Isolation

Input to output:

250V ac rms

Input and output to power supply:

250V ac rms

U

m

= 250V rms

INPUT

Input voltage

19.2 - 30V dc

Current consumption:

235mA (typical) 330mA (max.) at 20V
190mA (typical) 265mA (max.) at 24V
155mA (typical) 215mA (max.) at 30V

Power dissipation with 110mA laod:

2.9W (typical) 4.3W (max.)

Input protection
Fuse + supply reversal diode

9121-IS FISCO POWER
SUPPLY - IIC

*

When used in accordance with IEC/TS 60079-27, there is no need to take into
consideration Co and Lo.

Note: Temperature coefficient 12mV/°C. If operated below 0°C, the reduced resistance of
the fieldbus cable more that compensates for the reduction in voltage available.

Fieldbus Foundation™ and FOUNDATION™ are trademarks of Fieldbus Foundation, Austin, Texas, USA.

The applicable fieldbus specifications and standards are:
— FOUNDATION™ Fieldbus 31.25 kb/s Physical Layer Profile

Specification, document FF-816.

IEC 61158-2: 2000.

ISA-S50.02-1992 for 31.25 kb/s fieldbus systems.