Topologies, Fieldbarrier – VEGA FIELDBARRIER User Manual

Page 17

Advertising
background image

FieldBarrier

Subject to reasonable modifications due to technical advances.

Copyright Pepperl+Fuchs, Printed in Germany

Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com

08/

2007 122329

15

5.2.3

Topologies

Fieldbus topologies are independent of whether an H1 fieldbus segment of the
FOUNDATION fieldbus or a PROFIBUS MBP segment is being operated.

The basic layout of a fieldbus with FieldBarriers is illustrated in Figure 5.1.

Two cable types with the following components are essentially recommended for both
fieldbus systems:

The use of FieldBarriers influences possible topologies. For more
detailed information, please refer to chapter 6.2.

Type A

Type B

Cable structure

twisted wire

pair, shielded

One or more twisted

pairs, total shielding

Conductor cross-section (nominal)

0.8 mm²

(AWG 18)

0.32 mm² (AWG 22)

Loop resistor (direct current)

44

Ω/km

112

Ω/km

Wave resistance at 31.25 kHz

100

Ω + 20%

100

Ω + 30%

Wave attenuation at 39 kHz

3 dB/km

5 dB/km

Capacitive asymmetry

2 nF/km

2 nF/km

Group runtime distortion (7.9 ... 39) kHz

1.7 µs

a

a. not specified

Covering level of the shield

90%

a

Maximum extent of the network for non-

intrinsically safe applications

1900 m

1200 m

Maximum extent of the network for intrinsi-

cally safe applications

1000 m

a

Segment coupler

PROFIBUS MBP(-IS)

Bus termination
resistor

PROFIBUS DP

or
Power repeater

or H1 bus of the
FOUNDATION
fieldbus

or H1 bus (IS) of the
FOUNDATION
fieldbus

Spur

Spur

Spur

Trunk

Advertising