Specification, Installation, Approvals to order specify – VEGA TP32 Series User Manual

Page 2

Advertising
background image

+ve

-ve

Earth

Specification

All figures typical at 25°C (77°F) unless otherwise stated

Maximum surge current

10kA peak (8/20µs waveform)

Leakage current

Line-line:

< 1µA at working voltage

Line-earth:

< 1µA at 120V common-mode

Working voltage

±32V dc maximum
±120V peak (or DC) maximum common-mode

Maximum continuous operating voltage

35V

Limiting voltage

Line-line with 250mm cable:
< 49V (10A, 10/1000µs pulse)
Line-earth with 75mm cable:
<635V (3kA, 8/20µs waveform)
<635V (6kV, 1.2/50µs waveform)

Line resistance

No resistance introduced into the loop

Capacitance

Line-line:

< 50pF

Line-earth:

< 100pF

Attenuation

7·8KHz–7.5MHz monotonic & better than –1dB
typical bandwidth, 150MHz on 100Ω system

Ambient temperature limits

T6

–40°F to +140°F (–40°C to +60°C)

T5

–40°F to +185°F (–40°C to +85°C)

Humidity

5% to 95% RH (non-condensing)

Electrical connections

3 flying leads: line 1 & line 2 plus

non-polarised earth

Wire size:

32 / 0.2 (1.0mm

2

, 18 AWG)

Lead length:

250mm minimum supplied
≤ 75mm recommended

Casing

ANSI 316 stainless steel hexagonal barstock,
male thread

Threads

TP32-N

1

/

2

” NPT

TP32-I

20mm ISO (M20 x 1.5)

TP32-G

G

1

/

2

” (BSP

1

/

2

inch)

Weight

175g (6.18oz)

Dimensions

See figure 1

ATEX compliance

See Approvals table for details

EMC compliance

BS EN 61643-1

Electrical Safety

EEx ia IIC T6, Ceq=0, Leq=0; the unit can be
connected without further certification into any
intrinsically safe loop with open circuit voltage
<60V and input power <1.2W.
EEx d IIC T6; the unit is apparatus-approved to
explosionproof (flameproof) standards, and can
be fitted into a similarly approved housing.

Installation

The TP32 is designed for mounting directly into an
unused conduit entry on a fieldbus transmitter
housing (see figure 2). Generally, two such entries are
provided, one of which is used for the bus wiring. On
the unused entry, the blanking plug or other closure
device is removed and an appropriately threaded
TP32 screwed into its place. The transmitter
specification should provide information indicating the
required thread type. TP32 units can be installed
using thread adaptors (such as a tee piece) if
necessary, including certified adaptors in hazardous
area applications. For applications where two conduit
entries are not provided or where both are used for
electrical connections, TP32 units can be housed in
conventional conduit hub or junction boxes, provided
access to the loop terminals is possible.

904-023 0

1

75mm
(2.95")

27mm
(1.07")

55mm
(2.17")

Lead length

250mm (9.85")

minimum supplied

23mm
(0.91")

Dimensions across flats 23mm (0.91")

Figure 1 Dimensions

Figure 2 Connection detail for a typical transmitter

Approvals

To order specify -

TP32-N

1

/

2

” NPT thread

TP32-N-NDI

1

/

2

” NPT thread, with EEx ia, EEx d, FM and CSA approval

TP32-I

20mm ISO thread

TP32-I-NDI

20mm ISO thread, with EEx ia, EEx d, FM and CSA approval

TP32-G

G

1

/

2

” (BSP

1

/

2

inch)

TP32-G-NDI

G

1

/

2

” (BSP

1

/

2

inch), with EEx ia, EExd, FM and CSA approval

Note: In accordance with our policy of continuous improvement, we reserve the right to change the product’s specification without notice.

Telematic and Atlantic Scientific surge protection devices
are designed and manufactured by MTL Surge Technologies.

MTL Surge Technologies
Power Court, Luton, Bedfordshire, England LU1 3JJ
Tel: +44 (0)1582 723633 Fax: +44 (0)1582 422283
E-mail: [email protected] WWW: www.mtlsurge.com

A member of the MTL Instruments Group plc

Country

Standard

Certificate/File Approved

for

Product

(Authority)

No.

UK (BASEEFA)

EN 50014:1997 + Amendments 1 & 2

BAS00ATEX1258X

EEx ia IIC T6 (T

amb

= -40 to 60°C)

TP32-N-NDI

EN 50020:1994, EN 50284:1999

EEx ia IIC T5 (T

amb

= -40 to 85°C)

TP32-I-NDI

TP32-G-NDI

UK (BASEEFA)

EN 50014:1997 + Amendments 1 & 2

BAS00ATEX2146X

EEx d IIC T6 (T

amb

= -40 to 60°C)

TP32-N-NDI

EN 50018:2000

EEx d IIC T5 (T

amb

= -40 to 85°C)

TP32-I-NDI

TP32-G-NDI

Atex Directive

To be confirmed

TML02ATEX0032X

Ex n II T6 (-40°C<T

amb

<+60°C)

TP32-N

94/9/EC

Eex n II T5 (-40°C<T

amb

<+85°C)

TP32-I

TP32-G

USA (FM)

Class Nos. 3600 (1998), 3610 (1999),

311208

Intrinsically Safe:

TP32-N-NDI

3611 (1999), 3615 (1989), 3810 incl.

I, II, III/1/A-G, I/0/IIC

TP32-I-NDI

Supp 1 (1995-07 (1989-03),

Explosionproof: I/1/A-D

TP32-G-NDI

ANSI/NEMA 250 (1999),

Non incendive: I/2/A-D, I/2/IIC

ISA0S12.0.01 (1998)

Dust ignition proof: II,III/1/EFG
Special protection: II/2/FG

Canada (CSA)

C22.2 No. 30

152423

Class I, Grp A-D

TP32-N-NDI

C22.2 No. 1010

(LR 36637)

Class II, Grp E-G

TP32-I-NDI
TP32-G-NDI

F M

APPROVED