Profibus-pa power link module kld2-pl(2)-1.pa 2 – VEGA KLD2-PL(2)-1.PA PROFIBUS-PA Power Link Module User Manual

Page 2

Advertising
background image

PROFIBUS-PA Power Link Module

KLD2-PL(2)-1.PA

2

Subject to reasonable modifications due to technical advances.

Copyright Pepperl+Fuchs, Printed in Germany

Pepperl+Fuchs Group · Tel.: Germany (6 21) 7 76-22 22 · USA (3 30) 4 25 35 55 · Singapore 7 79 90 91 · Internet http://www.pepperl-fuchs.com

P000357E

01/01 02

Dimensions

115

92,5

107

Removable terminals green

80

Protective cap,
remove when power is supplied by Power Rail

Power Rail

Adjustable extensions

Removable terminals green

Technical Data
Power
Nominal voltage

DC 20 V ... 35 V

Ripple

£ 10 %

Current consumption

790 ... 400 mA

PROFIBUS-PA

PROFIBUS-PA

Nominal voltage U

S

24 ... 26 V

Maximum current I

S

400 mA

Terminator impedance

100 Ohm, integrated

Master channel
Baud rate

31.25 kbit/s for connection to KLD2-GT...

Cable length min.

852 m at maximum output current and cable type A, 0.8 mm

2

(AWG 18)

Galvanic Isolation
PROFIBUS-PA - Master channel

Function isolation per EN 50 178, design isolation voltage is 50 V

eff.

PROFIBUS-PA - power supply

Function isolation per EN 50 178, design isolation voltage is 50 V

eff.

Master channel - power supply

Function isolation per EN 50 178, design isolation voltage is 50 V

eff.

All circuits - FE (terminal 46)

Function isolation per EN 50 178, design isolation voltage is 50 V

eff.

All circuits - screen/FF (terminals 1, 13)

Function isolation per EN 50 178, design isolation voltage is 50 V

eff.

Conformity to Standards
Environmental conditions

DIN IEC 60 721-2-1 1992

EMC

NAMUR NE 21

1998

DIN EN 50 081-2

1994

EN 61 326

1999

Isolation coordinates

EN 50 178

1998

Fieldbus Standards

IEC 61158-2

1993

ISA S 50.02 Part 2

1992

Environmental Conditions

per DIN IEC 721

Class

3K3

Ambient temperature

253 K ... 333 K (-20 °C ... +60 °C / -4

°F ... 140 °F)

Storage temperature

233 K ... 358 K (-40 °C ... +85 °C / -40

°F ... 185 °F)

Protection method per DIN 40 050

IP 20

High relative humidity

75 %

Ambient conditions

max. grime accumulation level 2 per IEC 664

Mechanical
Design

Makrolon modular housings, flammability class per UL 94: V - 0

Installation

Can be snapped onto a 35 mm DIN rail per DIN EN 50 022 or wall mounted

Connectivity

Adjustable, removable device terminals with a max. diameter of 2.5 mm

2

(14 AWG)

Weight

about 600 g

Accessories
Power Rail,

PR 05

Insert for standard rail per DIN EN 50 022, normal length is 500 mm

Power feed module,

KFD2-EB2.B

supplies Power Rail with a voltage of DC 24 V and a max. current of 4 A

Fieldbus Terminator,

KMD0-FT-Ex

closes the PROFIBUS-PA branch in the field. The KMD0-FT-Ex is connected to the last
PROFIBUS-PA I/O.

Bridge station,

KLD2-GT(2)-DP(R).xPA

Bridge for PROFIBUS-DP (up to 12 Mbit/s)

I/O Number,

The max. combined current consumption of the connected I/Os must be lower

I/O Current Consumption:

than the nominal current I

S

of the segment coupler. The modulation current used by an I/O

to send data, does not need to be observed.

Models:

KLD2-PL-1.PA

Power Link Module

KLD2-PL2-1.PA

Power Link Module for installation within Zone 2

Advertising