8

4 Connecting to power supply

VEGABAR 81 • Slave sensor for electronic differential pressure

46331-EN-131125

4 Connecting to power supply

4.1 Connecting

The voltage supply and signal output are connected via the spring-

loaded terminals in the housing.
Connection to the display and adjustment module or to the interface

adapter is carried out via contact pins in the housing.
Information:

The terminal block is pluggable and can be removed from the

electronics. To do this, lift the terminal block with a small screwdriver

and pull it out. When reinserting the terminal block, you should hear it

snap in.

Proceed as follows:
1. Unscrew the housing cover
2. If a display and adjustment module is installed, remove it by turn-

ing it slightly to the left.

3. Loosen compression nut of the cable entry gland
4. Remove approx. 10 cm (4 in) of the cable mantle, strip approx.

1 cm (0.4 in) of insulation from the ends of the individual wires

5. Insert the cable into the sensor through the cable entry

Fig. 3: Connection steps 5 and 6

6. Insert the wire ends into the terminals according to the wiring plan
Information:

Solid cores as well as flexible cores with wire end sleeves are insert-

ed directly into the terminal openings. In case of flexible cores without

end sleeves, press the terminal from above with a small screwdriver,

the terminal opening is then free. When the screwdriver is released,

the terminal closes again.
You can find further information on the max. wire cross-section under

"Technical data/Electromechanical data"

Connection technology

Connection procedure