Profibus pa distributor with screw connection, Circuit diagram, Technical data – VEGA PROFIBUS PA T-Connector User Manual

Page 7: Installation advice, Ordering data

Advertising
background image

56

The overvoltage protection ensures safe discharge against earth potential

Screen is connected with the housing
by the cable gland

off: no Bus Terminator

(delivery status)

on: Bus

Terminator

active

Terminal on pcb

PROFIBUS-PA PA +

Screen (clamp)

PROFIBUS-PA PA -

4-pole socket connector M12*1

C1 1.0 µF
63V =

B

S

A

B

S

100R

B

S

A

n.c. A

Ш

Ш

Ш

Ш

Ш

Ш

S

S

C20,01 F

R1100R

C11,0 F

A

S

B

A

B

APROFIBUS-P AP A-

BPROFIBUS-P AP A+

4-pole socket connector M12*1

n.c.

PROFIBUS PA distributor with screw connection

off: no Bus Terminator

(delivery status)

on: Bus

Terminator

active

off: no Bus Terminator

(delivery status)

on: Bus

Terminator

active

Terminal on pcb

PROFIBUS-PA PA +

PROFIBUS-PA PA -

C1 1.0 µF
63V =

B

S

A

B

S

100R

B

A

A

Wire

Circuit diagram

Terminal on pcb

4-pole socket connector M12*1

Circuit diagram

C1 1.0 µF
63V =

C2 0.01 µF
250V ~

B

S

A

B

S

100R

B

S

A

n.c. A

Terminal on pcb

PROFIBUS-PA PA +

PROFIBUS-PA PA -

PROFIBUS-PA
field-bus cable

PA -

PA +

37

< 25

Screen

64

58

Pressure

compensati-

on element

< 20

< 25

Technical data

Temperature range

Operating temperature

- 40 to 85 ºC

Type of protection

IP 66

Material of housing

high-quality aluminium alloy (AL - Si 12)

Surface

stove-enamelled RAL 7001

PROFIBUS-PA - Connection

Screw terminals 0.5 - 1.5 mm

2

(AWG 26 - 16)

Cable bushing

Cable gland PG 9 / Clamping range 4.0 - 8.0 mm

Measuring instrument connector Contact brass,

M12 x 1 4-pole

Surface CuZnAu

Voltage arrestor, optional

90 V ignition voltage DC / 700 V at 1 kV/µS

2.5 KA discharge current 8/20 µs

Installation advice

Torques screw terminals

0.4 Nm

Torques cable gland on housing

6.0 Nm

Coupling ring PG cable gland

4.0 Nm

Housing lid

1.8 - 2.0 Nm

Adapter/stub cable

hand-tight

External earthing cable

1.8 - 2.0 Nm

(The use of a cable shoe is recommended) Connection according to circuit diagram

PROFIBUS-PA T-Connector standard

PROFIBUS-PA T-Connector with 3 PG cable glands

Circuit diagram

Circuit diagram

PROFIBUS-PA T-Connector with 2 EMC cable glands

PROFIBUS-PA T-Connector with overvoltage protection

PG 9

M12 connector

Earthing
screw M4

Ordering data

Type

Cat. No.

PROFIBUS-PA T-Connector standard

8426000000

Ordering data

Type

Cat. No.

PROFIBUS-PA T-Connector with 2 EMC cable glands

8426010000

Ordering data

Type

Cat. No.

PROFIBUS-PA T-Connector with 3 PG cable glands

9455940000

Ordering data

Type

Cat. No.

PROFIBUS-PA T-Connector with overvoltage protection

8426020000

Advertising