Wiring distance table: typical application diagram – Altronix StrikeIt2 Installation Instructions User Manual

Page 5

Advertising
background image

StrikeIt2

- 5 -

--- OUT

+

AC LED

UNLOCK

L G N

GND NO -- BAT + -- Aux +

Trg

Panic Hardware Device

24VDC

REX PIR

Access

Control

Panel

+

---

Rechargeable

Batteries

12VDC

+

---

12VDC

115VAC power mains

non power-limited

6.3A

250V

Fig. 1

Wiring Distance Table:

Typical Application Diagram:

InRush
Current

Wire Gauge

Electric Butt or Pivot

Max distance from Power Supply to frame side of opening

EPT

Max distance from Power Supply to frame side of opening

8 amp

14 AWG Stranded

75 ft.

100 ft.

8 amp

12 AWG Stranded

175 ft.

200 ft.

12 amp

14 AWG Stranded

60 ft.

75 ft.

12 amp

12 AWG Stranded

80 ft.

100 ft.

16 amp

14 AWG Stranded

40 ft.

75 ft.

16 amp

12 AWG Stranded

60 ft.

80 ft.