Altronix AL400ULXB2 Installation Instructions User Manual

Al400ulxb2 ul recognized power supply/charger

Advertising
background image

Power Supply Voltage Output Selections:

Output

Switch Position

12VDC

SW1 - CLOSED (Fig. 1, on the right)

24VDC

SW1 - OPEN (Fig. 1, on the right)

Stand-by Specifications:

Output

4 hr. of Stand-by &

5 Minutes of Alarm

24 hr. of Stand-by &

5 Minutes of Alarm

60 hr. of Stand-by &

5 Minutes of Alarm

12VDC / 40AH Battery

Stand-by = 4.0 amp

Alarm = 4.0 amp

Stand-by = 1.0 amp

Alarm = 4.0 amp

Stand-by = 300mA

Alarm = 4.0 amp

24VDC / 12AH Battery

--------

Stand-by = 200mA

Alarm = 3.0 amp

--------

24VDC / 40AH Battery

Stand-by = 3.0 amp

Alarm = 3.0 amp

Stand-by = 1.0 amp

Alarm = 3.0 amp

Stand-by = 300mA

Alarm = 3.0 amp

Installation Instructions:

The AL400ULXB2 should be installed in accordance with article 760 of The National Electrical Code or NFPA 72
as well as all applicable Local Codes.
1. Mount the AL400ULXB2 in the desired location/enclosure.
2. Set the AL400ULXB2 to the desired DC output voltage by setting SW1 (Fig. 2, pg. 2) to the appropriate position
(refer to Power Supply Voltage Output Selections chart).
3. Connect AC power (115VAC 60Hz) to the terminals marked [L, G, N] (Fig. 2, pg. 2). Use 18 AWG or larger for all
power connections (Battery, DC output, AC input). Use 22 AWG to 18 AWG for power-limited circuits
(AC Fail/Low Battery reporting).

Keep power-limited wiring separate from non power-limited wiring (115VAC / 60Hz Input, Battery Wires).

Minimum 0.25” spacing must be provided.
4. Connect devices to be powered to the terminals marked [+ DC –] (Fig. 2, pg. 2).
5. Measure output voltage before connecting devices. This helps avoiding potential damage.
6. For Access Control applications batteries are optional. When batteries are not used, a loss of AC will result in the
loss of output voltage. When the use of stand-by batteries is desired, they must be lead acid or gel type.
Connect battery to the terminals marked [+ BAT –] (Fig. 2, pg. 2). Use two (2) 12VDC batteries connected in series
for 24VDC operation (battery leads included).

AL400ULXB2

UL Recognized Power Supply/Charger

Agency Listings:

• UL Recognized component for: Access Control
System Units (UL 294), Power Supplies for use with
Burglar-Alarm Systems (UL 603), Hospital Signaling
and Nurse Call Equipment (UL 1069), Power Supplies
for Fire Protective Signaling Systems (UL 1481).

Input Rating:

• Input 115VAC 60Hz, 3.5 amp.

Output Rating:

• Class 2 Rated power-limited output.
• 12VDC or 24VDC selectable output.
• 12VDC @ 4 amp or 24VDC @ 3 amp continuous
supply current.
• Filtered and electronically regulated output.

Battery Backup:

• Built-in charger for sealed lead acid or gel type batteries.
• Maximum charge current 0.7 amp.
• Automatic switch over to stand-by battery when AC fails.
• Zero voltage drop when switched over to battery backup.

Visual Indicators:

• AC input, DC output and Battery LED indicators.

Supervision:

• AC fail supervision (form “C” contacts).
• Low battery and battery presence supervision
(form “C” contacts).

Additional Features:

• Short circuit and thermal overload protection.

Board Dimensions (W x L x H approximate):

4.5” x 7.1” x 1.44” (114mm x 180mm x 37mm)

OPEN SWITCH

CLOSED SWITCH

Switch Detail

+

DC

---

NC C NO NC C NO

+

BA

T

---

AC DC Bat

Risk of Fire,
Replace Fuses
As Marked

Opened - 24V

Closed - 12V

AC Fail

Bat Fail

J1

SW1

5A 250V

15A 250V

AC Delay

15

L

G

N

Fig. 1

Overview:

The AL400ULXB2 is a power supply/charger that converts a 115VAC 60Hz input into a Class 2 Rated power-limited
12VDC or 24VDC output (see specifications).

Specifications: