Altronix T2428100 Installation Instructions User Manual

Altronix Accessories for electrical

Advertising
background image

Altronix is not responsible for any typographical errors. Product specifications are subject to change without notice.

140 58th Street, Brooklyn, New York 11220 USA, 718-567-8181, fax: 718-567-9056
website: www.altronix.com, e-mail: [email protected], Made in U.S.A.
IIT2428100 - Rev. 061010

F10J

T2428100 - Open Frame Transformer

Specification Chart:

Model #

Input (Primary)

Output (Secondary)

Agency Listing

T2428100

115VAC 60Hz (1 amp)

24VAC/100VA (4 amp)
or 28VAC/100VA (3.5 amp)

Installation Instructions:

1. Mount transformer in desired location/enclosure (refer to Transformer Dimensions below).
2. Connect AC power to the primary leads (refer to Wiring Configuration below).

Use 18 AWG or larger for all power connections.

3. Measure output voltage across the secondary leads:

- Yellow and Brown for 24VAC (open circuit voltage @ 115VAC approx. 26.1VAC).

- Black and Brown for 28VAC (open circuit voltage @ 115VAC approx. 30.4VAC).

before connecting devices (refer to Wiring Configuration below). This helps avoid potential damage.

4. Connect 24VAC device(s) to Yellow and Brown leads or 28VAC device(s) to Black and Brown leads

(refer to Wiring Configuration below).

WARNING: This installation should be made by qualified service personnel and should
conform to all local codes and in accordance with the National Electrical Codes.

Wiring

Configuration:

Leads are approximately 8” long.

Transformer Dimensions:

Model #

A

B

C

D

E

F

Approx. Ship Wt.

T2428100

3.08”

2.65”

2.25”

1.39”

3.966”

3.565”

2.3 lbs.

SECONDARY

PRIMARY

28VAC

(Black)

Black

Lead

White

Lead

115VAC, 60Hz Input

24VAC

(Yellow)

Com

(Brown)

PRIMARY

SECONDARY

F

A

B

D

C

E

Advertising