Specifications:

• Input voltage: 12VDC or 24VDC max. 8 amps.
• Low voltage cutoff: 12VDC: 10.5 volts (+/--- 0.3 volts) 24VDC: 20 volts (+/--- 0.3 volts).
• Restore voltage threshold: 12VDC: 11.5 volts (+/--- 0.3 volts) 24VDC: 23 volts (+/--- 0.3 volts).
• Relay contact rating 8 amp max.
Board dimensions: 2.75"L x 2.2"W x 1"H

Operation:

Normal Condition: INPUT + connects via relay contact to OUTPUT +.
Low Voltage disconnect: INPUT + from OUTPUT + during low voltage cutoff.
Note: INPUT --- remains connected to OUTPUT --- at all times.

Voltage Selection Chart:

Installation Instructions:

1. Mount LPD in desired location/enclosure.
2. Set the LPD to desired operating voltage via SW1 & SW2 (see Voltage Selection Chart).
3. Connect output from power supply to terminals marked [+ INPUT --- ].
4. Connect devices to be powered to terminals marked [--- OUT +].

---

O

U

T

+

SW2

+

IN

P

U

T

---

DEVICES

(Max. 8 amps)

DC
OUTPUT

---

+

---

+

SW1

Altronix is not responsible for any typographical errors. Product specifications are subject to change without notice.

140 58th Street, Brooklyn, New York 11220 USA, 718-567-8181, fax: 718-567-9056
web site: www.altronix.com, e-mail: [email protected], Lifetime Warranty, Made in U.S.A.
IILPD - Rev. 062408

MEMBER

Output Voltage

SW1

SW2

12VDC

Open

Closed

24VDC

Closed

Open