Maximal11D/Maximal33D/Maximal55D/Maximal77D/Maximal75D Access Power Controllers (PTC)

- 7 -

Power Supply Board Terminal Identification:

Terminal
Legend

Function/Description

L, G, N

Connect 115VAC 60Hz to these terminals: L to hot, N to neutral.

+ DC -

Maximal11D - 12VDC @ 3.5 amp or 24VDC @ 2.7 amp to ACM8CB boards (power-limited).
Maximal33D - 12VDC @ 5.5 amp or 24VDC @ 5.7 amp to ACM8CB boards (power-limited).
Maximal55D - 12VDC @ 9.5 amp to ACM8CB boards (power-limited).
Maximal77D - 24VDC @ 9.7 amp to ACM8CB boards (power-limited).
Maximal75D - one (1) power supply which is 12VDC @ 9.5 amp to ACM8CB board (power-limited)
and one (1) power supply which is 24VDC @ 9.7 amp to ACM8CB board (power-limited).

AC FAIL

NC, C, NO

Indicates loss of AC power. To meet with UL requirements it is mandatory to connect visual notification

devices, connecting audible notification devices is optional. Relay normally energized when AC power is

present. Contact rating 1 amp @ 28VDC. AC or brownout fail is reported within 1 minute of event.

BAT FAIL
NC, C, NO

Indicates low battery condition, e.g. connect to access control panel. Relay normally energized when
DC power is present. Contact rating 1 amp @ 28VDC. A removed battery is reported within 5 minutes.
Battery reconnection is reported within 1 minute.
Low battery threshold:
12VDC output threshold set @ approximately 10.5VDC.
24VDC output threshold set @ approximately 21VDC.

+ BAT -

Stand-by battery connections. Connect one (1) 12VDC battery to the terminals marked [+ BAT -]
for 12VDC operation (Fig. 3, pg. 10, Fig. 5, pg. 12). Use two (2) 12VDC batteries wired in series for
24VDC operation (Figs. 3-5, pgs. 10-12).

Access Power Controller Terminal Identification:

Terminal Legend

Function/Description

- Control +

12VDC or 24VDC input from power supply board.

- Power +
(only applicable for
Maximal11D)

These terminals can be connected to an external UL Listed power-limited access control
power supply to provide isolated operating power for the ACM8CB (jumpers J1 and J2
Must be removed). All field wiring connections must be made employing suitable gauge
CM or FPL jacketed wire (or equivalent substitute), (Figs. 6a-9a, pgs. 13-16).

TRIGGER
INPUT 1-INPUT 8
IN, GND

From normally open and/or open collector sink trigger inputs
(request to exit buttons, exit pir’s, etc.)

OUTPUT 1-OUTPUT 8
NC, C, NO, COM

12VDC to 24VDC trigger controlled outputs:
Fail-Safe [NC positive (+) & COM Negative (-)],
Fail-Secure [NO positive (+) & COM Negative (-)],
Auxiliary output [C positive (+) & COM Negative (-)]
(When using AC power supplies polarity need not be observed),
NC, C, NO convert to dry form “C” 5 amp 24VAC/VDC rated dry outputs when PTCs
are removed. Contacts shown in a non-triggered state.

FACP INTERFACE
T, + INPUT --

Fire Alarm Interface trigger input from FACP. Trigger inputs can be normally open,
normally closed from an FACP signaling circuit output (Figs. 10-15, pg. 17).

FACP INTERFACE
NC, C, NO

Form “C” relay contact rated @ 1 amp 28VDC for alarm reporting (not evaluated by UL).