Overview:

OLS120 power supply/charger converts 115VAC, 60Hz or 230VAC, 50Hz input into a 12VDC or 24VDC @ 4 amp of
continuous supply current (see specifications). This general purpose power supply has a wide range of applications for
access control and security system accessories that require additional power.

Specifications:

Voltage Output Selection Table:

Output VDC

Switch Position Max. Load DC

12VDC

SW 1 - Closed

4 amp

24VDC

SW1 - Open

4 amp

Installation Instructions:

The OLS120 should be installed in accordance with The National Electrical Code and all applicable Local Regulations.
1. Mount the OLS120 in the desired location/enclosure.
2. Slide [Power ON/OFF] switch t o OFF position.
3. Set the OLS120 to the desired DC output voltage via SW1 (Voltage Output Selection Table).
4. Connect AC power to the terminals marked [L & N], connect ground to the terminal marked [G].

Use 18 AWG or larger for all power connections (Battery, DC output).

Use 22 AWG to 18 AWG for power-limited circuits (AC Fail/Low Battery reporting).

5. Measure output voltage before connecting devices. This helps avoiding potential damage.
6. Connect devices to be powered to the terminals marked [-- DC+].
7. When the use of stand-by batteries is desired, they must be lead acid or gel type.

Connect battery to the terminals marked [-- BAT +] (battery leads included).

Use two (2) 12VDC batteries connected in series for 24VDC operation.

8. When batteries are not used, a loss of AC will result in the loss of output voltage.
9. Connect appropriate signaling notification devices to AC Fail & Low battery supervisory

relay outputs marked [NC, C, NO].

10. Slide [Power ON/OFF] switch to ON position.

OLS120 - Offline Power Supply/Charger

Input:

• Universal input 115VAC, 50/60Hz, 0.95 amp
or 230VAC, 50/60Hz, 0.6 amp.

Output:

• 12VDC or 24VDC selectable output.
• 4 amp continuous supply current.
• Filtered and electronically regulated output.
• Short circuit and thermal overload protection.

Battery Backup:

• Built-in charger for sealed lead acid or
gel type batteries.
• Automatic switch over to stand-by battery
when AC fails.
• Maximum charge current 0.7 amp.

Supervision:

• AC fail supervision (form “C” contacts).
• Low battery supervision (form “C” contacts).

Visual Indicators:

• AC input and DC output LED indicators.

Features:

• Power ON/OFF switch.
• Includes battery leads.

Board Dimensions (approx.):

7.25” (184.1mm) x 4.5” (114.3mm) x 1.75” (44.45mm).