Altronix AL1002ULADA Data Sheet User Manual

Al1002ulada nac power extenders

Advertising
background image

Agency Listings:

• UL Listed Control Units for Fire Protective

Signaling Systems (UL 864).

• MEA - NYC Department of Buildings Approved.

• CSFM - California State Fire Marshal Approved.

• FM - Factory Mutual Approved.

• NFPA 72 Compliant.

Input:

• Power input 120VAC 60 Hz, 5 amp.

• Two (2) Class A, Style Z or two (2) Class B,

Style W, Y FACP inputs.

• Two (2) NC dry contact trigger inputs.

Output:

• Class 2 Rated power limited outputs.

• 24VDC @10 amp max total alarm current.

• 2.5 amp max current per output.

• Separate 1.0 amp auxiliary output.

• Programmable supervised indicating circuit outputs:

Four (4) Class B, Style W, Y or Two (2) Class A,

Style Z or One (1) Class A, Style Z and Two (2) Class

B, Style W, Y

• Thermal and short circuit protection with auto reset.

Battery Backup:

• Built-in charger for sealed lead acid or gel type bat-

teries.

• Automatic switchover to stand-by battery when

AC Fails.

• Zero voltage drop when switching over to

battery backup.

Supervision:

• AC fail supervision (form “C” contact, 1 amp / 28VDC).

Factory set for 30 seconds with optional 2.5 to 3 hour

delay setting (field selectable).

• Instant local AC trouble reporting relay

(form “C” contact, 1 amp / 28VDC).

• Battery presence and low battery supervision

(form “C” contact, 1 amp / 28VDC).

Visual Indicators:

• Input and output status LED indicators.

Special Features:

• 2-wire horn/strobe Sync mode allows audible

notification appliances (horns) to be silenced

while visual notification appliances (strobes)

continue to operate.

• Sync protocols include Potter/Amseco, Faraday,

Gentex

®

,

System Sensor

®

, and CooperWheelock

®

.

• Temporal Code 3, Steady Mode, Input to Output

Follower Mode (maintains synchronization of

notification appliances circuit).

• Compatible with 12VDC or 24VDC fire panels.

• Output loop supervision steered to input 1 or input 2.

• Signal circuit trouble memory (helps identify

intermittent loop problems).

• Common trouble input and output.

• Ground fault detection.

• Unit includes power supply, red enclosure, cam lock,

and battery leads.

Mechanical:

• Enclosure Dimensions (H x W x D approx.):
15.5” x 12” x 4.5” (393.7mm x 304.8mm x 114.3mm)

• Product weight (approx.): 12 lbs. (5.44 kg).

• Shipping weight (approx.): 13.3 lbs. (6.03 kg).

AL1002ULADA

NAC Power Extenders

Rev. AL1002ULADA_090402013

Overview

Specifications

Agency Approvals

UL Listed Control Units and Accessories
for Fire Alarm Systems (UL 864) Ninth
Edition

Factory Mutual Approved.

NYC Department of Buildings Approved.

California State Fire Marshal Approved.

Altronix Corp.

140 58th St. Brooklyn, NY

AL1002ULADA are extremely cost effective voltage regulated remote NAC
Power Extenders. They may be connected to any 24 volt Fire Alarm Control
Panel (FACP). Primary applications include Notification Appliance Circuit
(NAC) expansion (supports ADA requirements) and providing auxiliary
power to support system accessories.

AL1002ULADA

Advertising