Altronix AL600ULACMCB Data Sheet User Manual

Altronix Accessories for electrical

Advertising
background image

Overview

The AL600ULACMCB converts a 115VAC 60Hz input into eight (8) independently
controlled 12VDC or 24VDC Fail-Safe and/or Fail-Secure outputs with a total of 6 amp
continuous supply current. Outputs are activated by an open collector sink or normally
open (NO) dry trigger input from an Access Control System, Card Reader, Keypad, Push
Button, PIR, etc. This unit will route power to a variety of access control hardware devices
including Mag Locks, Electric Strikes, Magnetic Door Holders, etc. The outputs will
operate in both Fail-Safe and/or Fail-Secure modes. This unit is designed to be powered
by one common power source (factory installed) which will provide power for both the
board operation and locking devices, or two (2) totally independent power sources, one (1)
providing power for board operation and the other for lock / accessory power. The FACP
Interface enables Emergency Egress, Alarm Monitoring, or may be used to trigger other
auxiliary devices. The fire alarm disconnect feature is individually selectable for any or all
of the eight (8) outputs.

AL600ULACMCB

Power Supply/Chargers w/Multi-Output

Access Power Controllers

Rev. DSAL600ULACMCB_01032013

Specifications

Input:

• Input 115VAC 60Hz rated @ 3.5 amp.
• Power supply input options:
a) One (1) common power input for ACM8CB and
lock power (factory installed).
b) Two (2) isolated power inputs - One (1) to power
the ACM8CB and one (1) for lock accessory power,
(external power supply is required). (Current is
determined by the power supply connected, not to
exceed a maximum of 10 amp total).
• Eight (8) Access Control System trigger inputs.
Input options:
a) Eight (8) normally open (NO) inputs.
b) Eight (8) open collector inputs.
c) Any combination of the above.

Output:

• 12VDC or 24VDC @ 6 amp supply current.
• Class 2 Rated power limited outputs.
• Eight (8) independently controlled outputs.
Output options:
a) Eight (8) Fail-Safe and/or Fail-Secure power outputs.
b) Eight (8) form “C” 5 amp rated relay outputs
c) Any combination of the above.
• Eight (8) auxiliary power outputs (unswitched)
• Output ratings:
- PTCs are rated @ 2.5 amp.
• Filtered and electronically regulated outputs
(built-in power supply).

Features:

• Fire Alarm disconnect (latching or non-latching) is
individually selectable for any or all of the
eight (8) outputs.
• Fire Alarm disconnect input options:
a) Normally open (NO) or normally closed (NC)
dry contact input.
b) Polarity reversal input from FACP signaling circuit.

Features (cont’d):

• Alarm output relay indicates that FACP input is
triggered (form “C” contact rated @ 1 amp 28VDC).
• Short circuit and thermal overload protection.
• AC fail supervision (form “C” contact).

Visual Indicators:

• Red LEDs indicate outputs are triggered
(relays energized).
• Green LED indicates FACP disconnect is triggered.
• AC input and DC output LED indicators.

Battery Backup:

• Built-in charger for sealed lead acid or gel type batteries.
• AL600ULXB (Power Supply Board) maximum
charge current 0.7 amp.
• Automatic switch over to stand-by battery when AC fails.
• Zero voltage drop when unit switches over to battery
backup (AC failure condition).
• Battery fail and battery presence supervision
(form “C” contact).

Electrical:

• Operating temperature: 0º C to 49º C ambient.
• ACM8CB board main fuse is rated at 10 amp.
• BTU/Hr.:
- 12VDC: 36.85 BTU/Hr.
- 24VDC: 73.70 BTU/Hr.

Mechanical:

• Enclosure Dimensions (L x W x H approx.):
15.5” (393.7mm) x 12” (304.8mm) x 4.5” (114.3mm).
• Enclosure accommodates up to two (2) 12AH batteries.
• Product weight (approx.): 10.3 lbs. (4.67 kg).
• Shipping weight (approx.): 11.6 lbs. (5.26 kg).

AL600ULACMCB