SMP3PM

- 1 -

SMP3PM - Supervised Power Supply/Charger

Overview:

SMP3PM is a supervised power supply/charger that converts a low voltage AC input, into a 12VDC or 24VDC

selectable output, with 2.5 amp of continuous supply current (see specifications).

Specifications:

Voltage Output/Transformer Selection Table:

Output VDC Switch Position Max. Load DC Transformer Requirements
12VDC

SW1 Closed

2.5 amp

16VAC/40VA (TP1640), 24VAC or 28VAC/100VA (T2428100)

24VDC

SW1 Open

2.5 amp

24VAC or 28VAC/100VA (T2428100)

Note: Transformers with higher VA ratings may be used for all output voltages above as long as you

do not exceed 28VAC or 45VDC.

Installation Instructions:

The SMP3PM should be installed in accordance with The National Electrical Code

and all applicable Local Regulations.

1. Mount the SMP3PM board in desired location/enclosure.

2. Set the SMP3PM to desired DC output voltage via SW1 (Voltage Output/Transformer Selection Table).

3. Connect proper transformer to terminals marked [AC] (Voltage Output/Transformer Selection Table).

Use 18 AWG or larger for all power connections (Battery, DC output).

Use 22 AWG to 18 AWG for power limited circuits (AC Fail/Low Battery reporting).

4. Measure output voltage before connecting devices. This helps avoid potential damage.

5. Connect devices to be powered to terminals marked [ + DC -- ].

6. When the use of stand-by batteries are desired, they must be lead acid or gel type.

Connect battery to terminals marked [ + BAT -- ] on the board (battery leads included).

Use two (2) 12VDC batteries connected in series for 24VDC operation.

Note: When batteries are not used a loss of AC will result in the loss of output voltage.

7. Connect appropriate signaling notification devices to AC Fail & Low battery supervisory

relay outputs marked [NC, C, NO].

LED Diagnostics:

Red (DC)

Green (AC)

Power Supply Status

ON

ON

Normal operating condition

ON

OFF

Loss of AC, Stand-by battery supplying power.

OFF

ON

No DC output.

Off

Off

Loss of AC, Discharged or no standby by battery. No DC output.

Input:

• 16VAC to 28VAC
(Voltage Output/Transformer Selection Table).

Output:

• 12VDC or 24VDC selectable output.
• 2.5 amp supply current.
• Filtered and electronically regulated outputs.
• Short circuit and thermal overload protection.

Battery Backup:

• Built-in charger for sealed lead acid or
gel type batteries.
• Maximum charge current 0.3 amp.
• Zero voltage drop when switching over
to battery backup.

Supervision:

• AC fail supervision (form “C” contacts).
• Low battery supervision (form “C” contacts).

Indicators:

• AC input and DC output LED indicators.

Additional Features:

• Includes battery leads.

Board Dimensions

(L x W x H) (approximate)

:

• 4.05” (102.87mm) x 7” (177.8mm) x 1.35” (34.29mm)