Maximal11 distributes and switches power to access control systems and accessories. It con-
verts a 115VAC 60Hz input into sixteen (16) independently controlled 12VDC or 24VDC
fuse protected outputs. These Fail-Safe/Fail-Secure power outputs may be converted to dry
form “C” contacts. The outputs are activated by an open collector sink or normally open
(NO) dry trigger input from an Access Control System, Keypad, Push Button, REX PIR,
etc. Units will route power to a variety of access control hardware devices including: Mag
Locks, Electric Strikes, Magnetic Door Holders, etc. The FACP Interface enables Emer-
gency Egress, Alarm Monitoring, or may be used to trigger other auxiliary devices. The fire
alarm disconnect feature is individually selectable for any or all of the sixteen (16) outputs.
All interconnecting equipment must be UL Listed.

Overview

Maximal11

Specifications

Input:

• 115VAC 60Hz, 7.0 amp input.

• Power supply input options:

a) Two (2) common power input for either ACM8

and lock power (factory installed).

b) Two (2) isolated power inputs (external power

supply is required), (current is determined by the

power supply connected, not to exceed a

maximum of 10 amp total).

• Sixteen (16) Access Control System trigger inputs.

Input options:

a) Sixteen (16) normally open (NO) inputs.

b) Sixteen (16) open collector inputs.
c) Any combination of the above.

Output:

• 12VDC and/or 24VDC outputs.

• Maximum output current:

Options

P/S 1

P/S 2

A

12VDC @ 3.5 amp

12VDC @ 3.5 amp

B

24VDC @ 2.7 amp

24VDC @ 2.7 amp

C

12VDC @ 3.5 amp

24VDC @ 2.7 amp

• Class 2 Rated power limited outputs.

• Sixteen (16) independently controlled outputs.

Output options:

a) Sixteen (16) Fail-Safe and/or Fail-Secure

power outputs.

b) Sixteen (16) form “C” 5 amp rated relay outputs.

c) Any combination of the above.

• Sixteen (16) auxiliary power outputs (unswitched)

(outputs are rated 2.5 amp).

• Filtered and electronically regulated outputs (built-in

power supply).
• Thermal and short circuit protection with auto reset.

Fuse Ratings:

• Power Supply input fuse rated @ 3.5 amp/250V.

• ACM8 boards main fuse is rated at 10 amp.
Output fuses are rated @ 3.5 amp.

Features:

• Fire Alarm disconnect (latching or non-latching) is

individually selectable for any or all of the

sixteen (16) outputs.

• Fire Alarm disconnect input options:

a) Normally open (NO) or normally closed (NC) dry

contact input.

b) Polarity reversal input from FACP signaling circuit.

• Alarm output relay indicates that FACP input is

triggered (form “C” contact rated @ 1 amp 28VDC).

• AC fail supervision (form “C” contact).

• Low battery and battery presence supervision
(form “C” contact).

Battery Backup:

• Built-in charger for sealed lead acid or gel type

batteries.

• Maximum charge current 0.7 amp per p/s board.

• Automatic switch over to stand-by battery when

AC fails.

• Zero voltage drop when unit switches over to battery
backup (AC failure condition).

Visual Indicators:

• Red LEDs indicate outputs are triggered

(relays energized).

• Green LED indicates FACP disconnect is triggered.
• AC input and DC output LED indicators.

Electrical:

• Operating temperature: 0º C to 49º C ambient.

• BTU/Hr.:

- 12VDC: 43 BTU/Hr.

- 24VDC: 66.33 BTU/Hr.

- 12VDC & 24VDC: 54.66 BTU/Hr.
• System AC input VA requirement: 805VA.

Mechanical:

• Enclosure Dimensions (H x W x D approx.):
26” x 19” x 6.25” (660.4mm x 482.6mm x 158.75mm)
• Enclosure accommodates up to
four (4) 12AH batteries.

• Product weight (approx.): 43 lbs. (19.5 kg).

• Shipping weight (approx.): 47 lbs. (21.32 kg).