Altronix RBOC7 Installation Instructions User Manual

Rboc7 - open collector multiple relay module, Specifications, Installation instructions

Advertising
background image

RBOC7 - Open Collector Multiple Relay Module

Specifications:

• 12VDC or 24VDC selectable operation.
• Seven (7) independent (3VDC to 24VDC @ 2mA

minimum) positive inputs.

• Seven (7) open collector outputs capable of

sinking 100mA each.

Board dimensions: 6.5"L x 3.25"W x 1"H

Installation Instructions:

1. Mount unit in desired location/enclosure.
2. Connect positive trip outputs to desired trigger

inputs. INP1 to INP7 activate outputs on positive
trip signal of 3VDC to 24VDC @ 2mA.

3. Open collector outputs are marked “OC”.

Open collector output specs:
Sink current: 100mA.
Maximum output voltage: 50VDC.

INP5

INP6

INP7

GND POS+

INP1

INP2

INP3 INP4

GND

MULTIPLE RELAY MODULE

ALTRONIX CORP.

BROOKLYN, NY 11220

RBOC7

NO

C

NO

C

NO

C

NO

C

NO

C

NO

C

NO

C

Altronix is not responsible for any typographical errors. Product specifications are subject to change without notice.

140 58th Street, Brooklyn, New York 11220 USA, 718-567-8181, fax: 718-567-9056
website: www.altronix.com, e-mail: [email protected], Lifetime Warranty, Made in U.S.A.