Open Frame Transformers

Altronix is not responsible for any typographical errors. Product specifications are subject to change without notice.

140 58th Street, Brooklyn, New York 11220 USA, 718-567-8181, fax: 718-567-9056
website: www.altronix.com, e-mail: [email protected], Made in U.S.A.
IIT24130D/T2885D - Rev. 031008

C10H

MEMBER

Specification Chart:

Installation Instructions:

1. Mount transformer in desired location/enclosure.
2. Connect 115VAC or 220VAC power to the primary wires as shown in the Input Wiring Configuration

below (Fig. 1a or 1b).

3. Measure output voltage across the secondary wires from terminal numbers 6 and 10, as shown in the Output Wiring

Configuration below (Fig. 2), before connecting devices. This helps avoid potential damage.

4. Connect 24VAC (T24130D) or 28VAC (T2885D) devices to be powered to the secondary wires from terminal

numbers 6 and 10, as shown in the Output Wiring Configuration below (Fig. 2).

WARNING: This installation should be made by qualified service personnel and should
conform to all local codes and in accordance with the National Electrical Codes.

Input Wiring Configuration:

Transformer Dimensions:

Fig. 3

10

6

PRIMARY TERMINALS

SECONDARY TERMINALS

F

5 4

2 1

A

B

D

C

E

Fig. 1a

Fig. 1b

Output Wiring Configuration:

Fig. 2

5

4

3

2

1

5

4

3

2

1

220VAC Input

115VAC Input

24VAC or 28VAC Output

10

9

8

7

6

Model #

Input

Output

T24130D

115VAC 50/60Hz .9 amp or 220VAC 50/60Hz .45 amp

24VAC/100VA (4.16 amp)

T2885D

115VAC 50/60Hz .9 amp or 220VAC 50/60Hz .45 amp

28VAC/100VA (3.57 amp)

Model #

A

B

C

D

E

F

Approx. Ship Wt.

T24130D

3.06”

2.56”

2.25”

1.31”

4”

3.625”

1.12 lbs.

T2885D

3.57”

2.56”

2.25”

1.31”

4”

3.625”

1.12 lbs.