Altronix AL400UL Installation Instructions User Manual

Altronix Accessories for electrical

Advertising
background image

AL400UL

- 1 -

Overview:

The AL400UL power supply converts a 115VAC / 60Hz input to a 12VDC or 24VDC power-limited output
(see specifications). The AL400UL is UL Listed for fire alarm, burglar alarm, and access control applications.

Specifications:

Power Supply Voltage Output Selections:

Output Switch Position
12VDC SW1, 2 ON, SW3, 4 OFF
24VDC SW1, 2 OFF, SW3, 4 ON

Stand-by Specifications:

Output

4 hr. of Stand-by &
5 Minutes of Alarm

24 hr. of Stand-by &

5 Minutes of Alarm

60 hr. of Stand-by &

5 Minutes of Alarm

12VDC / 40AH Battery

Stand-by = 4.0 amp

Alarm = 4.0 amp

Stand-by = 1.0 amp

Alarm = 4.0 amp

Stand-by = 300mA

Alarm = 4.0 amp

24VDC / 12AH Battery

--------

Stand-by = 200mA

Alarm = 3.0 amp

--------

24VDC / 40AH Battery

Stand-by = 3.0 amp

Alarm = 3.0 amp

Stand-by = 1.0 amp

Alarm = 3.0 amp

Stand-by = 300mA

Alarm = 3.0 amp

Installation Instructions:

Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, and with all local
codes and authorities having jurisdiction. Product is intended for indoor use only.
1. Mount unit in the desired location. Mark and predrill holes in the wall to line up with the top two keyholes in the
enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place the enclosure’s
upper keyholes over the two upper screws; level and secure. Mark the position of the lower two holes. Remove the
enclosure. Drill the lower holes and install the fasteners. Place the enclosure’s upper keyholes over the two
upper screws. Install the two lower screws and make sure to tighten all screws (Enclosure Dimensions, pg. 4).
Secure enclosure to earth ground.
2. Set the AL400UL to the desired DC output voltage by setting dip switches (Fig. 1) to the appropriate position
(see Power Supply Voltage Output Specifications Chart).
3. Connect AC power (115VAC / 60Hz) to the black and white flying leads of the transformer(Fig. 1).
Use 18 AWG or larger for all power connections (Battery, DC output).
Use 22 AWG to 18 AWG for power-limited circuits (AC Fail/Low Battery reporting).

AL400UL - UL Listed, Multi-Agency Approved

Power Supply/Charger

Altronix Corp.

140 58th St. Brooklyn, NY

Agency Listings:

• UL Listed

Fire, Burglar and Access Control

Power Supply (UL1481, UL603, UL294).

• MEA - NYC Department of Buildings Approved.

• CSFM - California State Fire Marshal Approved.

• NFPA 72 compliant

Input:

• Input 115VAC, 60Hz, 3.5 amp.

Output:

• 12VDC or 24VDC selectable output.
• 12VDC @ 4 amp or 24VDC @ 3 amp supply current.
• Class 2 Rated power-limited output.
• Filtered and electronically regulated output.
• Short circuit and thermal overload protection.

Battery Backup:

• Battery leads included.
• Built-in charger for sealed lead acid or gel type batteries.
• Automatic switch over to stand-by battery when AC fails.
• Maximum charge current 1.2 amp.

Supervision:

• AC fail supervision (form “C” contacts).
• Low battery supervision (form “C” contacts).

Visual Indicators:

• AC input and DC output LED indicators.

Enclosure Dimensions (H x W x D approx.):

12.25” x 7.25” x 4.5” (311.15mm x 184.15mm x 114.3mm)

Advertising