Altronix AL400ULB Installation Instructions User Manual

Al400ulb ul recognized power supply/charger

Advertising
background image

Power Supply Output Specifications:

Output

VDC

Switch Position

Max. Stand-by

Load DC

Max. Alarm

Load DC

Stand-by Battery

12VDC

SW 1, 2 ON,

SW3, 4 OFF

4.0 amp

200mA

4.0 amp
4.0 amp

24V/40AH
12V/12AH

24VDC

SW 1, 2 OFF,

SW3, 4 ON

3.0 amp

200mA

3.0 amp
3.0 amp

24VDC

24V/12AH

Stand-by Specifications:

Output

4 hr. of Stand-by &
5 Minutes of Alarm

24 hr. of Stand-by &

5 Minutes of Alarm

60 hr. of Stand-by &
5 Minutes of Alarm

12VDC / 40AH Battery

Stand-by = 4.0 amp

Alarm = 4.0 amp

Stand-by = 1.0 amp

Alarm = 4.0 amp

Stand-by = 300mA

Alarm = 4.0 amp

24VDC / 12AH Battery

--------

Stand-by = 200mA

Alarm = 3.0 amp

--------

24VDC / 40AH Battery

Stand-by = 3.0 amp

Alarm = 3.0 amp

Stand-by = 1.0 amp

Alarm = 3.0 amp

Stand-by = 300mA

Alarm = 3.0 amp

Installation Instructions:

The AL400ULB should be installed in accordance with article 760 of The National Electrical Code or NFPA 72 as well
as all applicable Local Codes.
1. Mount AL400ULB in the desired location/enclosure.
2. Connect 28VAC / 175VA transformer to the terminals marked [AC, AC], (Fig. 1).
Use 18 AWG or larger for all power connections (Battery, DC output). Use 22 AWG to 18 AWG for the
power-limited circuits (AC Fail/Low Battery reporting).

Keep power-limited wiring separate from non power-limited wiring (115VAC / 60Hz Input, Battery Wires).

Minimum 0.25” spacing must be provided.
3. Set the AL400ULB to the desired DC output voltage by setting the switches to the appropriate positions
(Power Supply Output Specifications Table).
4. Connect devices to be powered to the terminals marked [+ DC – ] (Fig. 1).

AL400ULB

UL Recognized Power Supply/Charger

(AL400ULB Board)

Output Dip Switches

Overview:

The AL400ULB is a power-limited supply/charger that converts a 28VAC / 100VA input into a Class 2 Rated
power-limited 12VDC or 24VDC output (see specifications).

Specifications:

Agency Listings:

• UL Recognized component for Access Control
System Units (UL 294), Standard for Power
Supplies for Use with Burglar-Alarm Systems (UL 603),
Standard for Safety for Fire Protective Signaling

Systems (UL 1481).

Input:

• Input 28VAC / 100VA.

Output:

• Class 2 Rated power-limited output.
• 12VDC or 24VDC selectable output.
• 4 amp continuous supply current @ 12VDC.
• 3 amp continuous supply current @ 24VDC.
• Filtered and electronically regulated output.

Battery Backup:

• Built-in charger for sealed lead acid or gel type batteries.
• Maximum charge current 600mA.
• Automatic switch over to stand-by battery
when AC fails.

Visual Indicators:

• AC input and DC output LED indicators.

Supervision:

• AC fail supervision (form “C” contacts).
• Low battery supervision (form “C” contacts).

Additional Features:

• Short circuit and thermal overload protection.

Board Dimensions (W x L x H approximate):

4.1” x 7.1” x 1.75” (104.14mm x 180.34mm x 44.45mm)