Altronix AL125ULX Installation Instructions User Manual

Altronix Accessories for electrical

Advertising
background image

*Note: When unit is powered by battery back up (AC Fail condition) the voltage range is 9.3V-13.2V and

19.55V-26.4V for 12 and 24 volt operation respectively.

Power Supply Output Specifications: (AL125UL, AL125ULX)

Output VDC

Switch Position

Max. Stand-by Load DC

Max. Alarm Load DC

Battery (optional)

12VDC

SW2 Open

1 amp

1 amp

12VDC

24VDC

SW2 Closed

1 amp

1 amp

24VDC

Power Supply Output Specifications: (AL125ULP, AL125ULE)

Output VDC

Switch Position

Max. Stand-by Load DC

Max. Alarm Load DC

Battery (optional)

12VDC

SW2 Open

1 amp

1 amp

12VDC

24VDC

SW2 Closed

.5 amp

.5 amp

24VDC

Stand-by Specifications:

Output

4 hr. of Stand-by &

Output

4 hr. of Stand-by &

5 Minutes of Alarm

5 Minutes of Alarm

12VDC / 4AH Battery

.5 amp / 1 amp

12VDC / 7 AH Battery

1 amp / 1 amp

24VDC / 4 AH Battery

.5 amp / 1 amp

24VDC / 7 AH Battery

1 amp / 1 amp

Installation Instructions:

The units should be installed in accordance with article 760 of The National Electrical Code and NFPA 72 as well as all
applicable Local Codes.

Agency Listings:

• UL Listed for Access Control Systems (UL294).

CUL Listed - CSA Standard C22.2 No.205-M1983,
Signal Equipment.

• MEA - NYC Department of Buildings Approved.
• NFPA 101 (Life Safety).
Input:

• AL125UL, AL125ULX - 115VAC 50/60 Hz, .6 amp.
• AL125ULP, AL125ULE - 24VAC @ 40VA.
Output:

• Two (2) 12VDC or 24VDC, class 2 rated

power limited outputs.

• 1 amp total supply current @ 12VDC or 24VDC

(AL125UL & AL125ULX).

• 1 amp total supply current @ 12VDC, .5 amp total

supply current @ 24VDC (AL125ULP & AL125ULE).

• Filtered and electronically regulated output.*
Battery Backup:

• Built-in charger for sealed lead acid or

gel type batteries.

• Maximum charge current: 400mA.

Battery Backup (cont’d):

• Automatic switch over to stand-by battery when AC fails.
Special Features:

• AC power and unit status indicator on the front panel.
• Normally Open [NO] trigger input.
• Supervised Fire Alarm Disconnect (Latching w/reset

or Non-Latching).

Configurations:

• AL125UL - includes power supply, transformer

cam lock and enclosure (8.5”H x 7.5”W x 3.5”D).
Accommodates one (1) 12VDC/4AH battery.

• AL125ULP - includes power supply, plug-in transformer

(24VAC/40VA) cam lock and enclosure
(8.5”H x 7.5”W x 3.5”D). Accomodates one (1)
12VDC/7AH battery or two (2) 12VDC/4AH batteries.

• AL125ULE - includes power supply, cam lock

and enclosure (8.5”H x 7.5”W x 3.5”D).
Accommodates up to two (2) 12VDC/4AH batteries.

• AL125ULX - includes power supply, transformer,

cam lock and enclosure (13”H x 13.5”W x 3.25”D).
Accommodates up to two (2) 12VDC/7AH batteries.

Overview:

AL125UL, AL125ULX, AL125ULP, AL125ULE are Power Limited Power Supply/Chargers that will convert 115VAC
50/60Hz input, into two individually PTC protected 12VDC or 24VDC outputs (see specifications). They are intended
for use in applications requiring UL Listing for Access Control (UL294) and applications requiring an interface with Fire
Alarm Control Panels.

Specifications

AL125UL AL125ULX AL125ULP AL125ULE
Access Control Power Supply/Chargers

Rev. 050803

- 1 -