Altronix AL176ULX Installation Instructions User Manual

Al176ulx access control power supply/charger

Advertising
background image

Overview:

The AL176ULX is a power limited power supply/charger converts a 115VAC / 60Hz input, into 12VDC or 24VDC
output, (see specifications). They are intended for use in applications requiring UL Listing for Access Control (UL294).
It must be installed in accordance with National and Local Electrical Codes and Regulations.

Specifications:

• UL Listed - U.S. and Canada for Access Control Systems (UL294).
• MEA approved - NYC Dept. of Buildings.
• Class 2 rated power limited output.
• Input 115VAC/60Hz, .6 amp.
• Field selectable 12VDC or 24VDC power limited output.
• 1.75 amps continuous supply current @ 12VDC or 24VDC.
• Filtered and electronically regulated output.
• Maximum charge current: 400mA.
• Automatic switch over to stand-by battery when AC fails (zero voltage drop).
• AC fail supervision (form "C" 1 amp @ 28VDC).
• Low battery supervision (form "C" 1 amp @ 28VDC).
• AC input and DC output LED indicators.
• Short circuit and thermal overload protection.
• Unit includes: power supply, transformer and enclosure.
Enclosure Dimensions: 13”H x 13.5”W x 3.25”D

Power Supply Output Specifications:

Output VDC

Switch Position

Max. Stand-by Load DC

Max. Alarm Load DC

Battery (optional)

12VDC

Jumper Removed

1.75 amp

1.75 amp

12VDC

24VDC

Jumper On

1.75 amp

1.75 amp

24VDC

Stand-by Specifications:

Output

4 hr. of Stand-by &

5 Minutes of Alarm

12VDC / 7 AH Battery

Stand-by = 1.25 amp

24VDC / 7 AH Battery

Alarm = 1.25 amp

Installation Instructions:

The AL176ULX should be installed in accordance with article 760 of The National Electrical Code or NFPA 72 as well
as all applicable Local Codes.
See Terminal Identification Chart on page 3 for a description of each terminal function.
1. Mount the AL176ULX in desired location.
2. Connect AC power to the black and white flying leads of the transformer. Secure green wire lead to earth ground.

Use 18 AWG or larger for all power connections (Battery, AC input). Use 22 AWG to 18 AWG for power
limited circuits (DC output, AC FAIL and LOW BAT supervisory relays).
Keep power limited wiring separate from non-power limited wiring (115VAC / 60Hz Input, Battery Wires).
Minimum .25” spacing must be provided.

3. Set the AL176ULX to the desired DC output voltage by either removing/leaving jumper.

(Power Supply Output Specification Table).
Note: It is important to measure output voltage before connecting devices. this helps avoid potential damage.

4. Connect battery to terminals marked [+ BAT -] on the power supply board (battery leads included). Use two (2)

12VDC batteries connected in series for 24VDC operation.

Note: For Access Control applications, batteries are optional. When batteries are not used a loss of AC will result

AL176ULX
Access Control Power Supply/Charger