Agency Listings:

• UL Recognized component for: Access Control
System Units (UL 294), Power Supplies
for Fire Protective Signaling Systems (UL 1481).

Input:

• Input 115VAC 60Hz, 3.5 amp.

Output:

• 12VDC or 24VDC selectable non power-limited output.
• 6 amp continuous supply current.
• Filtered and electronically regulated output.

Battery Backup:

• Built-in charger for sealed lead acid or gel type batteries.
• Maximum charge current 0.7 amp.

Battery Backup (cont’d):

• Automatic switch over to stand-by battery when AC fails.
• Zero voltage drop when switched over to battery backup.

Visual Indicators:

• AC input, DC output and BAT trouble LED indicators.

Supervision:

• AC fail supervision (form “C” contacts).
• Low battery and battery presence supervision
(form “C” contacts).

Additional Features:

• Short circuit and thermal overload protection.

Board Dimensions (W x L x H approximate):

4.5” x 7.8” x 2.6” (114.3mm x 198.12mm x 66.04mm)

Power Supply Output Selections:

Output

Switch Position

12VDC

SW1 - CLOSED (Fig. 1, on the right)

24VDC

SW1 - OPEN (Fig. 1, on the right)

Stand-by Specifications:

Output

4 hr. of Stand-by &
5 Minutes of Alarm

24 hr. of Stand-by &

5 Minutes of Alarm

60 hr. of Stand-by &

5 Minutes of Alarm

12VDC / 40AH Battery

Stand-by = 6.0 amp

Alarm = 6.0 amp

Stand-by = 1.0 amp

Alarm = 6.0 amp

Stand-by = 300mA

Alarm = 6.0 amp

24VDC / 12AH Battery

--------

Stand-by = 200mA

Alarm = 6.0 amp

--------

24VDC / 40AH Battery

Stand-by = 6.0 amp

Alarm = 6.0 amp

Stand-by = 1.0 amp

Alarm = 6.0 amp

Stand-by = 300mA

Alarm = 6.0 amp

Installation Instructions:

The AL600ULXB should be installed in accordance with article 760 of The National Electrical Code as well as NFPA
72 and all applicable Local Codes.
1. Mount the AL600ULXB in the desired location/enclosure.
2. Set the AL600ULXB to the desired DC output voltage by setting SW1 (Fig. 1) to the appropriate
position (refer to Power Supply Output Selections chart).
3. Connect AC power (115VAC 60Hz) to the terminals marked [L, G, N] (Fig. 2). Use 18 AWG or larger for all
power connections (Battery, DC output, AC input).
Use 22 AWG to 18 AWG for power-limited circuits (AC Fail/Low Battery reporting).

Keep power-limited wiring separate from non power-limited wiring (115VAC / 60Hz Input, Battery Wires).

Minimum 0.25” spacing must be provided.
4. Measure output voltage before connecting devices. This helps avoiding potential damage.
Maximum ripple voltage rating is 0.8V.
5. Connect devices to be powered to the terminals marked [+ DC --- ] (Fig. 2).

AL600ULXB

UL Recognized Power Supply/Charger

Overview:

The AL600ULXB is a power supply/charger that converts a 115VAC 60Hz input into a 6 amp, 12VDC or 24VDC
non power-limited output (see specifications).

Specifications:

+ DC -

--

BAT FAIL NC C NO NC C NO

+ BA

T

---

AC FAIL

DC

AC

BAT

L

G

N

5A 250V

OPEN - 24V CLOSED - 12

V

Fig. 1

OPEN SWITCH

CLOSED SWITCH