Altronix AL300ULXD Installation Instructions User Manual

Page 3

Advertising
background image

AL300ULXD

- 3 -

Maintenance:

Unit should be tested at least once a year for the proper operation as follows:

Output Voltage Test: Under normal load conditions, the DC output voltage should be checked for proper voltage level
(Power Supply Output Selection chart).
Battery Test: Under normal load conditions, check that the battery is fully charged, check specified voltage both at bat-
tery terminal and at the board terminals marked [– BAT +] to ensure that there is no break in the battery connection wires.
Note: Maximum charging current under discharges is 600mA.
Note: Expected battery life is 5 years; however, it is recommended changing batteries in 4 years or less if needed.

LED Diagnostics:

Red (DC) Green (AC) Power Supply Status
ON

ON

Normal operating condition.

ON

OFF

Loss of AC, Stand-by battery supplying power.

OFF

ON

No DC output.

OFF

OFF

Loss of AC. Discharged or no stand-by battery. No Dc output.

Terminal Identification:

Terminal Legend Function/Description
AC/AC

Low voltage AC input (28VAC / 100VA).

+ DC –

12VDC / 24VDC @ 2.5 amp continuous power-limited output.

AC Fail
NC, NO, C

Indicates loss of AC power, e.g. connect to audible device or alarm panel. Relay normally ener-
gized when AC power is present. Contact rating 1 amp @ 28VDC. AC or brownout fail is report-
ed within 1 minute of event.

Bat Fail
NC, C, NO

Indicates low battery condition, e.g. connect to alarm panel. Relay normally energized when DC
power is present. Contact rating 1 amp @ 28VDC. A removed battery is reported within 5 min-
utes. Battery reconnection is reported within 1 minute.
Low battery threshold:
12VDC output threshold set @ approximately 10.5VDC,
24VDC output threshold set @ approximately 21VDC.

– BAT +

Stand-by battery connections. Maximum charge current 0.7 amp.

Advertising