Altronix AL600ULB Installation Instructions User Manual

Al600ulb ul recognized power supply/charger

Advertising
background image

AL600ULB

UL Recognized Power Supply/Charger

Overview:

The AL600ULB is a power supply that converts a 28VAC/200VA input to a 12VDC or a 24VDC output
(see specifications).

Specifications:

Power Supply Output Selection:

Output VDC Switch Position
12VDC

SW1 CLOSED

24VDC

SW1 OPEN

Stand-by Specifications:

Output

4 hr. of Stand-by &

5 Minutes of Alarm

24 hr. of Stand-by &

5 Minutes of Alarm

60 hr. of Stand-by & 5

Minutes of Alarm

12VDC / 40 AH Battery

Stand-by = 6 amp

Alarm = 6 amp

Stand-by = 1.0 amp

Alarm = 6 amp

Stand-by = 300mA

Alarm = 6 amp

24VDC / 12 AH Battery

------------

Stand-by = 200mA

Alarm = 6.0 amp

------------

24VDC / 40 AH Battery

Stand-by = 6 amp

Alarm = 6 amp

Stand-by = 1.0 amp

Alarm = 6 amp

Stand-by = 300mA

Alarm = 6 amp

Installation Instructions:

The AL600ULB should be installed in accordance with article 760 of The National Electrical Code as well as NFPA 72

and all applicable Local Codes.

1. Mount the AL600ULB in the desired location/enclosure.

2. Set the AL600ULB to the desired DC output voltage by setting SW1 to the appropriate position

(refer to Power Supply Output Selection chart).

3. Connect two (2) 28VAC/100VA transformers (connected in parallel) to the terminals marked [AC].

Use 14 AWG or larger for all power connections (Battery, DC output, AC input).

Use 22 AWG to 18 AWG for power-limited circuits (AC Fail/Low Battery reporting).

Keep power-limited wiring separate from non power-limited wiring (115VAC / 60Hz Input, Battery Wires).

Minimum 0.25” spacing must be provided.

4. Measure output voltage before connecting device. This helps avoiding potential damage.

5. Connect devices to be powered to the terminals marked [+ DC –] (Fig. 1, pg. 2).

When servicing the unit, AC mains should be removed.

6. For Access Control applications batteries are optional. When batteries are not used, a loss of AC will result in the

loss of output voltage. When the use of stand-by batteries is desired, they must be lead acid or gel type.

Connect battery to the terminals marked [+ BAT –] (Fig. 1, pg. 2).

7. Connect appropriate signaling notification devices to [AC FAIL & BAT FAIL] (Fig. 1, pg. 2) supervisory relay outputs.

Agency Listings:

• UL Recognized component for Access Control
System Units (UL 294), Standard for Safety
for Fire Protective Signaling Systems (UL 1481).

Input:

• Input 28VAC / 200VA.

Output:

• 12VDC or 24VDC selectable output.
• 6 amp continuous supply current @ 12VDC or 24VDC.
• Filtered and electronically regulated output.

Battery Backup:

• Built-in charger for sealed lead acid or gel type batteries.
• Maximum charge current 0.7 amp.

Battery Backup (cont’d):

• Automatic switch over to stand-by battery when AC fails.
• Zero voltage drop when switched over to battery backup.

Visual Indicators:

• AC input and DC output LED indicators.

Supervision:

• AC fail supervision (form “C” contacts).
• Low battery and battery presence supervision
(form “C” contacts).

Additional Features:

• Short circuit and thermal overload protection.

Board Dimensions (W x L x H approximate):

4.3” x 7.1” x 2.3” (109.22mm x 180.34mm x 58.42mm).

Advertising