Terminal identification, Application diagram, Fig. 1a - sw1 – Altronix AL125ULB Installation Instructions User Manual

Page 2: Fig. 1

Advertising
background image

Terminal Identification:

Terminal
Legend

Function/Description

XFMR

Low voltage transformer connections.

+AUX --

Aux power output terminals. These terminals will supply 12VDC or 24VDC,
not affected by trigger, reset or fire alarm interface.

LOCK+
STRIKE+
COM --

Switched power output. Fail-Safe [LOCK+] supplies positive power when unit is not
triggered and FACP interface is inactive. Fail-Secure [STRIKE+] supplies positive power
when unit is triggered and/or fire alarm interface is activated. [COM-- ] supplies
negative power.

FACP1
FACP2

Supervised by 2.2K end of line resistor FACP interface. Short or open will cause power to
be dropped to terminal marked [LOCK+] and supply power to terminal marked [STRIKE+].
Condition can be maintained even after restoration of the circuit (latching mode).

TRG INPUT
NO, GND

Short between these two terminals will cause power to be dropped to terminal marked

[LOCK+] and supplied to terminal marked [STRIKE+].

RESET
NO, GND

Momentary short between these terminals would end latching FACP interface condition
Feature active only if latching FACP is selected (SW1 closed).

+ BAT --

Stand-by battery connections.

Application Diagram:

Fig. 1

VR1

NO

NO

GND

GND

FACP1 FACP2

STRIKE+

COM--

LOCK+

+ AUX --

TRIG INPUT

RESET

S

W

1

+

B

A

T

--

X

F

M

R

SW2:
12VDC - Open
24VDC - Closed

Normal Open

Access Control

Triggering

Device

Normal Open
Reset Device

2.2K EOL

(supplied)

MAG LOCK

NC

FACP

NO

FACP

{

}

Card

Reader

Fig. 1A - SW1

O PEN SWITCH

CLOSED SWITCH