Intellimod™ Module
Dual-In-Line Intelligent Power Module
75 Amperes/600 Volts

Powerex, Inc., 173 Pavilion Lane, Youngwood, Pennsylvania 15697 (724) 925-7272

6

Rev. 08/09

Protection Function Timing Diagrams

a1

SC

SC REFERENCE VOLTAGE

RC CIRCUIT TIME CONSTANT DELAY

a2

a3

a4

a8

a5

a7

a6

SET

RESET

N-SIDE

CONTROL INPUT

PROTECTION

CIRCUIT STATE

INTERNAL IGBT GATE

SENSE VOLTAGE OF RS

OUTPUT CURRENT IC

FAULT OUTPUT FO

Short Circuit Protection (N-side Only with External Shunt Resistor and RC Filter)

a1: Normal operation – IGBT turns on and carries current.
a2: Short circuit current is detected (SC trigger).
a3: All N-side IGBT's gate are hard interrupted.
a4: All N-side IGBT's turn off.
a5: FO output wirh a fixed pulse width (determined by the external capacitance CFO).
a6: Input "L" – IGBT off.
a7: Input "H" – IGBT on, but during the FO output perid the IGBT will not turn on.
a8: IGBT turns on when L→H signal is input after FO is reset.

b1

b4

b5

b2

UVDt

b7

b3

SET

RESET

RESET

UVDr

b6

CONTROL INPUT

PROTECTION

CIRCUIT STATE

CONTROL SUPPLY

VOLTAGE VD

OUTPUT CURRENT IC

FAULT OUTPUT FO

Under-Voltage Protection (N-side , UVD)

b1: Control supply voltage VD rises – After VD level reaches under voltage reset level (UVDr), the circuits

start to operate when next input is applied.

b2 : Normal operation – IGBT turns on and carries current.
b3: VD level dips to under voltage trip level (UVDt).
b4: All N-side IGBT’s turn off in spite of control input condition.
b5: FO is low for a minimum period determined by the capacitance CFO but continuously during UV period.
b6: VD level reaches UVDr.
b7: Normal operation – IGBT turns on and carries current.