Ld41 – C&H Technology LD41__60 User Manual

Page 3

Advertising
background image

Powerex, Inc., 173 Pavilion Lane, Youngwood, Pennsylvania 15697 (724) 925-7272

POW-R-BLOK

TM

http://www.pwrx.com

Dual Diode Isolated Module

600 Amperes / Up to 2600 Volts

Revision Date: 01/14/2010

LD41__60






Absolute Maximum Ratings

Characteristics Conditions

Symbol

Units

Repetitive Peak Reverse Blocking Voltage

V

RRM

up to 2600

V

Non-Repetitive Peak Reverse Blocking Voltage
(t < 5 msec)

V

RSM

V

RRM

+ 100

V

RMS Forward Current

I

F(RMS)

950 A

Average Forward Current

180° Conduction, T

C

=106°C I

F(AV)

600 A

Peak One Cycle Surge Current, Non-Repetitive

60 Hz, 100% V

RRM

reapplied

50 Hz, 100% V

RRM

reapplied

I

FSM

I

FSM

21000
19000

A
A

Peak Three Cycle Surge Current, Non-Repetitive

60 Hz, 100%V

RRM

reapplied

I

FSM

15,500 A

Peak Ten Cycle Surge Current, Non-Repetitive

60 Hz, 100% V

RRM

reapplied

I

FSM

13,000

A

I

2

t for Fusing for One Cycle

8.3 milliseconds

10 milliseconds

I

2

t

I

2

t

1,840,000
1,810,000

A

2

sec

A

2

sec

Operating Temperature

T

J

-40 to +150

°C

Storage Temperature

T

stg

-40 to +150

°C

Max. Mounting Torque, M6 Mounting Screw

55

6

in. – Lb.

Nm

Max. Mounting Torque, M10 Terminal Screw

110

12

in. – Lb.

Nm

Module Weight, Typical

1500

g

3.30

lb

V Isolation @ 25C

V

rms

3000 V





































Advertising