PS22054
Intellimod™ Module
Dual-In-Line Intelligent Power Module
15 Amperes/1200 Volts

Powerex, Inc., 200 E. Hillis Street, Youngwood, Pennsylvania 15697-1800 (724) 925-7272

7

Rev. 10/05

Protection Function Timing Diagrams

C1

C4

C5

C2

UVDt

C6

C3

SET

RESET

RESET

HIGH LEVEL MEANS NO FO OUTPUT

UVDBr

CONTROL INPUT

PROTECTION

CIRCUIT STATE

CONTROL SUPPLY

VOLTAGE VDB

OUTPUT CURRENT IC

FAULT OUTPUT FO

Under-Voltage Protection (P-side, UVDB)

C1: Control supply voltage rises – After the voltage level reaches UVDBr, the drive circuit begins to work

at the rising edge of the next input signal.

C2: Normal operation – IGBT turn on and conducting current.
C3: Under-voltage trip (UVDBt).
C4: IGBT stays off regardless of the control input level, but there is no FO signal output.
C5: Under-voltage reset (UVDr).
C6: Normal operation – IGBT turn on and conducting current.

Typical Interface Circuit

Wiring Method Around Shunt Resistor

RSHUNT (Chip type resistor is recommended.)

VNC

NW

NV

NU

DIP-IPM

Wiring inductance should be less than 10nH.

This GND wiring from VNC should be as

close to the shunt resistors as possible.

UP, VP, WP, UN, VN, WN

MCU

5V LINE

10k

2.5k

Ω (MIN)

FO

VNC (LOGIC)

DIP-IPM

NOTE: RC coupling at each input
(parts shown dotted) may change
depending on the PWM control
scheme used in the application
and the wiring impedance of the
printed circuit board. The DIP-IPM
input signal section integrates a
2.5k

Ω (min) pull-down resistor.

Therefore, when using an external
filtering resistor, care must be
taken to satisfy the turn-on
threshold voltage requirement.