Milton CAT G300LG 300kW_375kVA Attenuated Enclosure Sound Data User Manual

Sound test results, Genset: enclosure

Advertising
background image

Genset:

Enclosure:

Right

Left

Notes:

1. All positions 23 ft (7M) from side faces of generator set.
2. Generator operating at full load.
3. Test conducted on a 100 foot diameter asphault surface.

Sound Test Results

G300LG 13.3L

Sound Attenuated Enclosure

Front

Back

Measured Sound Levels - 60 Hz

81.0

86.2

81.9

77.8

64

66

68

70

72

74

76

78

80

82

84

86

88

90

92

94

96

98

100

1

2

3

4

Position Number

dB

(A

) @ 7 Meter

s

Actual

Average

Avg. 81.7 dBA

RADIATOR END

GENERATOR END

Pos 1

Pos 2

Pos 3

Pos 4

DATA SUBJECT TO CHANGE WITHOUT NOTICE

0604840SSD 04/08