Milton CAT G250LG4 250kW_313kVA Open Sound Data User Manual

Sound test results, Genset: enclosure

Advertising
background image

Genset:

Enclosure:

Right

Left

Sound Test Results

G250LG 12.9L

Non-Enclosed Unit (Open Set)

Front

Back

Measured Sound Levels - 60 Hz

RADIATOR END

GENERATOR END

Pos 1

Pos 2

Pos 3

Pos 4

OLYMPIAN POWER SYSTEMS

DATA SUBJECT TO CHANGE WITHOUT NOTICE

0197490SSD 11/12

Notes:

1. All positions 23 ft (7M) from side faces of generator set.
2. Generator operating at full load.
3. Test conducted on a 100 foot diameter asphault surface.
4. Non-enclosed sets do not include exhaust sound during testing.

86.0

87.0

88.0

89.0

74

76

78

80

82

84

86

88

90

92

94

96

1

2

3

4

dB

(A

)

@ 7 M

e

ter

s

Position Number

Measured Sound Levels - 60 Hz

Actual

Average

Avg. 87.5 dBA

OLYMPIAN POWER SYSTEMS

DATA SUBJECT TO CHANGE WITHOUT NOTICE

0197490SSD 11/12