MAX16064

±0.3% Accurate, Quad, Power-Supply Controller with

Active-Voltage Output Control and PMBus Interface

______________________________________________________________________________________

39

VOUT_UV_FAULT_LIMIT (44h)

The VOUT_UV_FAULT_LIMIT command sets the value
of the output voltage measured across RS_+ and RS_-,
which causes an output undervoltage fault. This fault is
masked until the output voltage reaches the pro-
grammed voltage at startup, and also during turn-off
when the power supply is disabled.

The 2 data bytes are in DIRECT format. Valid values are
the same as VOUT_COMMAND.

The default VOUT_UV_FAULT_LIMIT value is 00h.

In response to violation of the VOUT_UV_FAULT_LIMIT,
the MAX16064:

1) Sets the OTHER bit in the STATUS_BYTE.

2) Sets the OTHER bit in the STATUS_WORD.

3) Sets the VOUT bit in the STATUS_WORD.

4) Sets the VOUT Undervoltage Fault bit in the

STATUS_VOUT register.

5) Sets the UV_FAULT bit in the STATUS_MFR_SPECIFIC

register.

6) Sets the UV_FAULT bit in the MFR_STATUS_WORD

register.

7) Sets the OTHER bit in the MFR_STATUS_WORD.

8) Responds as specified by VOUT_UV_FAULT_RESPONSE

bits in the MFR_FAULT_RESPONSE register.

9) Notifies the host using SMBALERT assertion.

OT_FAULT_LIMIT (4Fh)

The OT_FAULT_LIMIT command sets the temperature,
in degrees Celsius, of the on-chip temperature sensor
at which an overtemperature fault is detected.

The 2 data bytes are in DIRECT format. Valid values are
from -142.5°C to +395.4°C.

The default OT_FAULT_LIMIT value is 00h.

In response to the OT_FAULT_LIMIT being exceeded,
the MAX16064:

1)

Sets the TEMPERATURE bit in the STATUS_BYTE.

2)

Sets the TEMPERATURE bit in the STATUS_WORD.

3)

Sets the TEMPERATURE bit in the
MFR_STATUS_WORD.

4)

Sets the Overtemperature Fault bit in the
STATUS_TEMPERATURE.

5)

Sets the OT_FAULT bit in the MFR_STATUS_WORD
register.

6)

Responds as specified by OT_FAULT_RESPONSE
bits in the MFR_FAULT_RESPONSE register.

7)

Notifies the host using SMBALERT assertion.

OT_WARN_LIMIT (51h)

The OT_WARN_LIMIT command sets the temperature,
in degrees Celsius, of the on-chip temperature sensor
at which an overtemperature warning is detected.

The 2 data bytes are in DIRECT format. Valid values are
the same as the OT_FAULT_LIMIT.

The default OT_WARN_LIMIT value is 00h.

In response to the OT_WARN_LIMIT being exceeded,
the MAX16064:

1)

Sets the TEMPERATURE bit in the STATUS_BYTE.

2)

Sets the TEMPERATURE bit in the STATUS_WORD.

3)

Sets the TEMPERATURE bit in the
MFR_STATUS_WORD.

4)

Sets the Overtemperature Warning bit in the
STATUS_TEMPERATURE.

5)

Sets the OT_WARN bit in the MFR_STATUS_WORD
register.

6)

Notifies the host through SMBALERT using asser-
tion.

TON_DELAY (60h)

TON_DELAY sets the time, in milliseconds, from when a
start condition is received (a valid OPERATION com-
mand or through A3/CONTROL when enabled) until the
power-supply output voltage starts to rise. During
TON_DELAY, the power supply is disabled (ENOUT_
deasserted) until TON_DELAY expires. Also, the under-
voltage fault and warning are masked off during
TON_DELAY.

The 2 data bytes are in DIRECT format. Valid values are
from 0 to 3276.7ms.

The default TON_DELAY value is 0.

TON_RISE (61h)

The TON_RISE sets the time, in milliseconds, from
when the power-supply output voltage starts to rise until
the voltage has entered the regulation band. During
TON_RISE, the voltage and temperature-related faults
and warnings are masked off. Meanwhile, the
MAX16064 still responds to the PMBus command. If a
TON_RISE parameter results in the DAC outputting an
out-of-range value (valid range 0 to 4090) immediately
during TON_RISE, the CML flag is set and SMBALERT
asserts to issue a warning.