Site Wiring Fault

Alarm Code: 04

Site Fault detection is
supported on all models
anytime there is a
Grounding Neutral
connection.

Alarm triggers when the
difference between
ground and neutral
voltage is > 15v.

Site Fault detection should
be enabled by default. It can
still be enabled / disabled
from the LCD settings
menu.

Reconnect all input wires

Utility Abnormal

Alarm Code: 02

Utility is out of the
tolerance of input

Check input mains condition

Back feed

Alarm Code:93

UPS has a unexpected
bypass current on battery
mode

Transfer to maintenance
bypass and call service.

Battery Disconnect

Alarm Code:11

Battery voltage is lower
than the batteries
disconnected level
defined for this UPS. This
may be due to a blown
fuse, intermittent battery
connection or battery
cable being
disconnected.

Verify that all batteries are
properly connected.

If the condition persists,
contact your service
representative.

Battery low

Alarm Code:12

The UPS is in Battery
mode and the battery is
running low

This warning is
approximate, and the actual
time to shutdown may vary
significantly.

Depending on the UPS load
and number of Extended
Battery Modules(EBMs), the
“Battery Low” warning may
occur before the batteries
reach 25% capacity

Service Battery

Alarm Code:13

A faulted battery string
has been detected and as
a result the battery
charger has been
disabled until it is
replaced

Contact your service
representative