Monitoring software, Technical speicification – PowerWalker VI 400 IEC User Manual

Page 6

Advertising
background image

MODEL

PowerWalker

VI 400

PowerWalker

VI 600

PowerWalker

VI 800

CAPACITY

VA/W

400VA/240W

600VA/360W

800VA/480W

Voltage

110/120VAC or 220/230/240VAC

Voltage Range

85-140VAC or 162-290VAC

INPUT

Frequency

45-65 Hz (Auto Sensing)

Voltage (Batt. Mode)

110/120/220/230/240VAC +/-10%

Frequency (Batt. Mode)

50Hz or 60Hz +/-1 Hz

OUTPUT

Output Waveform

(line mode)Battery mode

Modified Sinewave Stepwave

Battery Type

12V4.5Ah x 1

12V7Ah x 1

12V9Ah x 1

Backup Time (at a PC

load with 15" monitor)

8 minutes

20 minutes

30 minutes

BATTERY

Recharge Time

8 hours to 90% after complete discharge

TRANSFER

TIME

Typical : 4-6 ms and 13ms(max)

AC Mode

Green lighting

INDICATOR

Backup Mode

Green flashing

Backup Mode

Sounding every 10 seconds

Low Battery

Sounding every second

AUDIBLE

ALARM

Overload

Sounding every 0.5 second

PROTECTION Full Protection

Discharge, overcharge, and overload protection

PHYSICAL

Dimension DxWxH(mm)

287x212x107

ENVIRONMENT Noise Level

Less than 40dB

Smart RS-232

Windows family, Sun Solaris, IBM Aix, Compaq

True64, UnixWare, FreeBSD, HP-UX, Linux and

MAC

INTERFACE

5. MONITORING SOFTWARE

After the UPS has been installed, you must install the
software(Smart Power) that came packaged with your
UPS. Smart Power monitoring software performs the
monitoring and controlling functions. This software
displays the status and diagnostic symptoms on the
monitor. In case of the power failure, it provides the auto
shutdown for the computer.

If you download the software from Internet, please key
the serial number: 726T25-4791-2N39546.

6. TECHNICAL SPEICIFICATION

9

10

Advertising