Fan fail

Fan abnormal

Check if the fan is running

Battery over voltage

Battery is over
charged

Switching to battery mode
automatically, and after the
battery voltage is normal
and the mains is normal, the
UPS would Switching to line
mode automatically again.

Battery low

Battery voltage is
low

When audible alarm
sounding every second,
battery is almost empty.

Charge fail

The charge is
broken

Notify dealer.

DC-DC temperature
high

Inside temperature
of the UPS is too
high

Check the ventilation of the
UPS, check the ambient
temperature.

Inverter temperature
high

Inside temperature
of the UPS is too
high

Check the ventilation of the
UPS, check the ambient
temperature.

Ambient temperature
high

The ambient
temperature is too
high

Check the environment
ventilation.

Line voltage high
(OVCD action)

Input power
voltage is too high

Switching to battery mode
automatically, and after the
mains is normal, the UPS
would Switching to line
mode automatically again.

Battery open

Battery pack is not
connected
correctly

Do the battery test to
confirm.
Check the battery bank is
connected to the UPS.
Check the battery breaker is
turn on.

Overload

Overload

Check the loads and
remove some non-critical
loads.
Check whether some loads
are failed.

Site fail

Phase and neutral
conductor at input

Rotate mains power socket
by 180° or connect UPS