Trouble shooting – PowerWalker ATS User Manual

Page 8

Advertising
background image

EN

8. Trouble Shooting

Use the table below to solve minor problems.

Problem

Possible Cause

Solution

The ATS with the

mains voltage

present, does don’t

turn on.

(The LEDs does not

flash and no alarm

sounds.)

No connection with

input plugs

Connect the mains to the input plugs as
indicated in the installation section.

Input switch in “OFF”

position

Turn the input switches in “ON” position.

Input power failure

Check that the mains voltage is present or
check if the UPS supplying the ATS is
powered on.

Protective device

upstream activated

Reset the protective device. Warning:
check that there is no overload or short-
circuit at the output of the UPS.

The load is not

powered.

No connection with

output sockets

Connect the load to the output sockets

Intervention of 10A

thermal protection

The thermal protection device will
operate in the event of a short circuit or
overload on one of the 10A output
sockets. The thermal protection can be
reset by pushing the button in which will
result in the power being reconnected to
the load. Therefore prior to attempting a
reset of the thermal protection, please
check the connected loads rating and/or
determine if there are any problems.
Then once reset, reconnect each load one
at a time to ensure no problems exists.

The display shows

nothing or provides

incorrect

information.

There is power supply

problem in display.

Shut down the ATS completely and wait
for a few seconds.
Switch the ATS on again, if the problem
persists, contact the nearest technical
support centre.

The display is off but

the load is powered.

There is power supply

problem in display.

Contact the nearest technical support
centre.


If there is any abnormal situations occur, which doesn't list above, please call the service people
immediately for professional examine.

Advertising