Powersolve PKR Series User Manual

Uninterruptible power supplies, Electrical specification

Advertising
background image

Powersolve Electronics Ltd.  8A Arnhem Road,  Newbury, RG14 5RU.  England

Tel: 01635 521858  Fax: 01635 523771  Email: [email protected]

UNINTERRUPTIBLE POWER SUPPLIES

Features

• Online Double Conversion Design
• High Input Power Factor
• Wide Input Voltage Range
• Automatic Bypass
• Intelligent RS232 Communication Port
• UPS Management Software
• External SNMP, USB or Dry Contacts (optional)
• External Battery Bank for increased Hold Up Time (optional)
• 19” Rack Mounting 1KVA 2U, 2KVA & 3KVA 4U,

6KVA 5U + 3U Battery Rack & 10KVA 5U + 2 X 3U Battery Racks

• Can also be mounted as stand alone tower unit.
• Fitted with Yuasa NPW45 Series batteries, optional 10 year life versions
• 5 year warranty (excluding batteries, unless 10 year life versions fitted)

Electrical Specification

INPUT

AC Input Range:

230VAC Input Model
115VAC Input Model

120-276VAC 50% load, 140-276VAC 75% load, 160-276VAC 100% load
80-138VAC all load conditions. 6kVA and 10kVA not available with 115VAC input

Power Factor:

>0.98

Total Harmonic Distortion:

≤5%

Input Frequency Range:

50/60Hz ±5%

Battery Voltage:

See table

OUTPUT
Power (VA):

See table

Power Factor:

0.7

Output Voltage & Frequency:

220/230/240VAC ±2% 50Hz or 110/120VAC ±2% 60Hz factory set

Waveform:

Pure sine wave

Total Harmonic Distortion:

<3% (linear load)

Overload:

105-130% for 60 Secs, 131-150% for 30 Secs, >150% for 300mS

Efficiency:

AC-AC 95%, Battery to AC 88%

TRANSFER TIME

AC to Battery Back Up:

Zero

Inverter to Bypass Mode:

4mS

BATTERY
Back Up Time:

See table

Charger Current:

4.5 Amp 1kVA to 3kVA models, 3 Amp 6kVA to 10kVA models

Recharge Time:

<3 hours to 90% or <4 hours for 6kVA & 10kVA (standard battery pack & charger)

Battery Type:

Yuasa NPW45-12, optional 10 year life versions

OTHER FEATURES
RS232 Port:

Supports UPS power management software or UPSilon 2000

SNMP (optional):

Power management from SNMP manager and Web browser

USB Port (optional):

Windows family

Dry Contacts:

DB9 Type or AS400 Card

Display:

LED indicates UPS status, LCD shows volts, frequency etc.

Alarm:

Low battery voltage, abnormal power supply, UPS failure

Protection:

Low battery voltage, overload, short circuit & over temperature

Audible Noise (dB):

<45dBA 1-3kVA models, <60dBA 6kVA & 10kVA models

Operating Temperature:

0 to 40ºC

Relative Humidity:

0-95% non condensing

Dimensions & Weights

See table

EMC:

EN61000-3-2, EN61000-3-3, EN50091-2 CE marked

Safety:

EN62040-1-1 for UPS Systems CE marked

PKR Series
1KVA to 10KVA 19” Rack Mounting

www.powersolve.co.uk

Advertising