Littelfuse PGR-6800 Series User Manual

Pgr-6800 series, Protection relays & controls, Motor protection–pumps (pgr 6000 family)

Advertising
background image

Protection Relays & Controls

© 2013 Littelfuse Protection Relays & Controls

Motor Protection–Pumps (PGR 6000 Family)

PGR-6800 SeRieS

Pump Protection Relay

Description

The PGR-6800 Pump Protection Relay provides protection for

pumps with three-phase motors up to 1,000 Vac. No current

transformers are required for currents up to 91 A. The protective

functions include overload, phase unbalance, phase loss, phase

sequence and undercurrent. The PGR-6800 Pump Protection

Relay is ideally suited for applications where operating without

load can induce failure. Motor current is monitored and an

undercurrent trip occurs when the current drops below a

preset level. No additional level detectors are required.

PGR-6800

SERIES

PGB-6800
(Remote Indication

and Reset Assembly)

(Pump Protection Relay)

M

L2

L1

ORdeRinG nuMbeR

COnTROL POWeR FuLL-LOad CuRRenT

PGR-6801-24

24 Vdc

7-19.6 A

PGR-6801-120

120 Vac

7-19.6 A

PGR-6801-240

240 Vac

7-19.6 A

PGR-6802-24

24 Vdc

19-44.2 A

PGR-6802-120

120 Vac

19-44.2 A

PGR-6802-240

240 Vac

19-44.2 A

PGR-6803-24

24 Vdc

40-90.4 A

PGR-6803-120

120 Vac

40-90.4 A

PGR-6803-240

240 Vac

40-90.4 A

Ordering Information

Simplified Circuit Diagram

PGB-6800 Remote Indication

and Reset Assembly

Optional remote indication of overload,

undercurrent, phase unbalance, phase loss,

and phase sequence. Remote reset included.

Accessories

A

A

aCCeSSORieS

RequiReMenT

PGB-6800

Optional

FeaTuReS

beneFiTS

No CTs required

No current transformers required for currents up

to 91 A

Adjustable trip

settings

Adjustable overload trip class setting from 5 to 15

for use with a wide variety of pumps

Output contacts

Form A and Form B ground-fault output contacts for

operation of separate annunciation and trip circuits

Remote indication

Cause-of-trip indication and reset button

Overload

Prevents insulation failures and fires; extends

motor life

Phase loss/Phase

sequence

Detects unhealthy supply conditions

Unbalance (current)

Prevents overheating due to unbalanced phases

Undercurrent

Detects low level or no-load conditions

Features & Benefits

Specifications

Protective Functions

(IEEE Device Numbers)


Input Voltage

See ordering information

Frequency

50, 60 Hz

Dimensions

H 83 mm (3.3”); W 78 mm (3.1”); D 99 mm (3.9”)

Test Button

Standard feature

Reset Button

Standard feature

Output Contacts

Isolated form A and Form B

Approvals

UL Listed (E343314)

Warranty

5 years

Mounting DIN

Overload (49, 51)
Phase sequence (46)
Undercurrent (37)

Unbalance (current) (46)
Phase loss (current) (46)

Littelfuse.com/pgr-6800

Rev: 4-A-050213

Based on Manual Rev 0