Littelfuse T2700 Series User Manual

T2700 series, Protection relays & controls, Generator & single-function protection–power

Advertising
background image

Protection Relays & Controls

© 2013 Littelfuse Protection Relays & Controls

Littelfuse.com/t2700

Generator & Single-Function Protection–Power

T2700 SerieS

Power Relay

Description

The T2700 Power Relay is intended for detection of power

levels for protection, control or monitoring purposes. The T2700

will protect a generator from excessive active loads [kW].
The T2700 calculates I x cos φ, representing the active power.

If the active power exceeds the preset level (15-150%), the

pick-up LED will indicate this and the delay timer will be started.

After the preset time (2-20 sec.) has expired, the output relay

and LED will be activated, provided that the active power level

was exceeded for the entire delay time.

Specifications

Trip Level

15-150% I

N

Delay

2-20 sec.

Max. Voltage

660 V

Voltage Range

60-110%

Consumption

Voltage 5 VA at U

N

Current 0.3 VA at I

N

Continuous Current

2 x I

N

Frequency Range

45-400 Hz

Output Relay

Normally de-energized, latching, resetable

Contact Rating

AC: 400 V, 5 A, 1250 VA; DC: 150 V, 5 A, 120 W

Overall Accuracy

±5%

Repeatability

±1%

Operating Temperature –20°C to + 70°C

EMC

CE according to EN50081-1, EN50082-1, EN50081-2,

EN50082-2

Approvals

Certified by major marine classification societies

Burn-in

50 hours before final test

Enclosure Material

Polycarbonate. Flame retardant

Weight

0.5 kg

Dimensions H

70 mm (2.76”); W 100 mm (3.94”); D 115 mm (4.52”)

Installation

35 mm DIN rail or 4 mm (

3

/

16

”) screws

Features & Benefits

FeaTureS

BeNeFiTS

Accepts high supply

voltage variation

Ensures correct operation in spite of voltage

supply fluctuations (fulfills marine class

requirement)

Visual indication of power,

pick-up, and output trip

Provides quick and concise status information

Direct line-line or line-

neutral voltage supply (up

to 690 Vac)

Simplifies design and installation.

No need for PTs.

Galvanic isolated inputs

Protects the unit against high AC voltage and

currents from the installation including spikes

DIN-rail or screw-mount

& adjustment by

potentiometers

Easy installation

9

5

C/B TRIP

10

6

L - L SUPPLY

7
8

1

3

2

RESET

13
14

LOAD

1

2

3

L

L

L

G

T2700

(Power

Relay)

9

5

C/B TRIP

10

6

L - N SUPPLY

7
8

1

3

2

RESET

13
14

LOAD

1

2

3

L

N

L

L

G

T2700

(Power

Relay)

Rev: 4-A-050213

Ordering Information

Simplified Circuit Diagram

Other supply voltages and combinations are available on request.

OrderiNG

NumBer

TermiNalS

i

N

SuPPly FuNcTiON

1-3

2-3

T2700.00

230 V

5 A L-N

T2700.02

450 V 400 V 5 A L-L

T2700.03

230 V 400 V 5 A L-L

T2700.04

110 V 100 V 5 A L-L

Normally energized output

T2700-08

127 V 120 V 5 A L-N

Advertising