Motor Protection System

Description

The PGR-6150 Motor Protection System provides 13 protective

functions by utilizing both current and temperature inputs. It is

a modular system consisting of the control unit and an operator

interface (PGR-6150-OPI). The OPI allows programming and

displays metered values. The PGR-6150 is used to provide

current- and temperature-based protection, metering and data

logging for three-phase motors used in industrial environments.

Current transformers are not required for currents up to 25 A.

Control Unit

g

Integrated phase CTs (external for applications > 25 A)

g

Ground-fault CT input

g

One PTC input and one programmable input

g

Two programmable output contacts

g

Eight status LEDs

g

RS-485 Communications

g

DIN-rail mountable

g

PC interface software

Operator Interface (optional)

g

Large, bright, LCD display

(2 x 20 alphanumeric characters)

g

Keypad for menu selection (system parameters,

measurements, and fault reports)

g

Displays metered values

g

Six user-programmable LEDs

g

Powered by Control Unit

g

1 meter (39-inch) connection cable included

ORdeRinG nuMbeR

COnTROL POWeR

PGR-6150-24 (Control Unit)

24/48 Vdc

PGR-6150-120 (Control Unit)

120/240 Vac/dc

PGR-6150-OPI (Operator Interface)

Powered by Control Unit

Ordering Information

NOTE: External CTs can be used for full-load currents >25 A.

PGR-6150-OPI Operator Interface

Optional Operator Interface for displaying

metered values and programming

PGC-6000 Series Ground-Fault Transformer

Optional zero-sequence current transformer,

used to measure ground-fault current.

Required for applications >25 A.

Accessories

A

B

aCCeSSORieS

RequiReMenT

PGC-6000 Series

Optional

1

1

A

A

Simplified Circuit Diagram

M

PGR-6150

PTC

(Operator Interface)

(Motor Protection System)

PGR-6150-OPI

L2

L1

GF CT

B

A

1

Littelfuse.com/pgr-6150

Rev: 4-A-050213

Based on Manual Rev 1