Axial Lead & Cartridge Fuses

3AB > High I

2

t > 328 Series

328 Series, Lead-Free 3AB, High Surge Withstanding Fuse

Agency Approvals

Features

• High surge withstanding

capability
– 20 hits of 10kA 8/20μs

surge

– Meets ANSI/IEEE

C62.41, Category
C-High

– Meets US Dept of

Energy (DOE) MSSLC/
CBEA street lighting
and parking lot
lighting, elevated level

• Small form factor

(6.3×32mm) with
cartridge and axial-lead
package options

• Breaking capacity:

200A@300VAC,
200A@100VDC

• Lead-free, RoHS

compliant, halogen-free

• Compliant with UL248-

14 and NFPA 70
(NEC) primary fusing
requirements

• Operating temperature:

–55°C to 125 °

Applications

Electrical Characteristics for Series

Agency

Agency File Number

Ampere Range

TUV

T5026058201

21A

E10480

21A

% of Ampere Rating

Opening Time

100%

4 hours, minimum

200%

120 sec., maximum

The – is a 300VAC rated, 10kA surge withstanding,
6.3×32mm ceramic fuse, designed in accordance to
UL248-14 Standard, provided in cartridge and axial-lead
packages.

Commercial and outdoor LED luminaries
Outdoor electronics and electrical equipment.
Surge protection for telecom application.

Description

Electrical Characteristic by ltem

Amp Rating

(A)

Voltage Rating

(VAC)

Interrupting

Rating

Surge

Rating

Nominal Cold

Resistance

(Ohms)

Nominal melting

I

2

t (A

2

sec)

Agency Approvals

TUV

21

300

200A@300VAC

200A@100VDC

1.2/50 - 8/20µs,

20kV/10kA 20

hits

0.0042

4,800

X

X

TUV

Additional Information

Datasheet

Samples

Resources