Cable limiters

600 VAC

LFCL - 500 - C - 1

Terminal Material

Littelfuse

Cable Limiter

Type of

Termination

Conductor Size

(Aluminum or Copper)

DesCription

Catalog number

type termination Cable size

Cable type

Cop per

aluminum

1

CAbLe tO CAbLe

4/0

LFCL4/0C1

LFCL4/0A1

250MCM

LFCL250C1

LFCL250A1

350MCM

LFCL350C1

LFCL350A1

500MCM

LFCL500C1

LFCL500A1

750MCM

LFCL750C1

LFCL750A1

3

CAbLe tO

OFFset bus

4/0

LFCL4/0C3

LFCL4/0A3

250MCM

LFCL250C3

LFCL250A3

350MCM

LFCL350C3

LFCL350A3

500MCM

LFCL500C3

LFCL500A3

750MCM

LFCL750C3

LFCL750A3

5

stRAiGht bus

tO OFFset bus

4/0

LFCL4/0C5

250MCM

LFCL250C5

350MCM

LFCL350C5

500MCM

LFCL500C5

750MCM

LFCL750C5

6

MOLe tO CAbLe

4/0

LFCL4/0C6

LFCL4/0A6

250MCM

LFCL250C6

LFCL250A6

350MCM

LFCL350C6

LFCL350A6

500MCM

LFCL500C6

LFCL500A6

750MCM

LFCL750C6

LFCL750A6

8

MOLe tO

OFFset bus

4/0

LFCL4/0C8

250MCM

LFCL250C8

350MCM

LFCL350C8

500MCM

LFCL500C8

750MCM

LFCL750C8

Note: For Type 5 and Type 8 Aluminum cable limiters, use the Copper Type C5 and C8.

Description

Cable limiters are fusible devices that provide very fast
short-circuit protection, primarily to faulted cables, but also to
other conductors such as busway. Cable limiters do not have
an ampere rating, and cannot be used to provide overload
protection. They are instead selected by cable size; for example,
a 500 kcmil cable requires a 500 kcmil cable limiter. Their
main use is to isolate faulted cables in circuits con tain ing
three or more parallel conductors per phase. They may be
installed on the line side of the main service to provide short-
circuit protection to the service conductors. This is especially
important when service conductors are tapped from large low
voltage networks or from large low impedance transformers.

Cable limiters have terminals which permit them to be installed
in a variety of equipment. The most common configuration is
the offset blade on one end and the crimp terminal on the other
end. This permits the limiter to replace a cable terminal (lug).

Applications

• Service entrance conductors
• Between transformer or network bus and busway

terminal boxes

• Large feeders with three or more conductors per phase

Features

• Current-limiting characteristics provide pro tec tion to

conductor insulation and reduce damage when faults occur.

• Properly applied cable limiters may permit the use of

equip ment with reduced withstand ratings

• Wide variety of terminations and cable ratings permit use

in almost every situation.

Specifications

Voltage Ratings

600 VAC

Interrupting Rating

200 kA

Cable Size Range

4/0 – 75MCM Copper or Aluminum

Note: For Type 5 and Type 8 Aluminum cable limiters, use the Copper Type C5 and C8.

Ordering Information

Web Resources

For additional information, see website:
www.littelfuse.com/lfcl