Littelfuse T2100 Series User Manual

T2100 series, Protection relays & controls, Excitation loss relay description

Advertising
background image

Protection Relays & Controls

© 2013 Littelfuse Protection Relays & Controls

9

5

C/B TRIP

10

6

L - L SUPPLY

7
8

1

3

2

RESET

13
14

LOAD

1

2

3

L

L

L

T2100

(Excitation

Loss

Relay)

G

9

5

C/B TRIP

10

6

L - N SUPPLY

7
8

1

3

2

RESET

13
14

LOAD

1

2

3

L

L

L

T2100

(Excitation

Loss

Relay)

G

Features

BeNeFIts

Accepts high supply

voltage variation

Ensures correct operation in spite of voltage

supply fluctuations (fulfills marine class

requirement)

Visual indication of

power, pick-up, and

output trip

Provides quick and concise status information

Direct line-line or line-

neutral voltage supply

(up to 690 Vac)

Simplifies design and installation.

No need for PTs.

Available with separate

24 Vdc supply

Safe operation. Maintains protection

regardless of system voltage failure

Galvanic isolated inputs

Protects the unit against high AC voltage and

currents from the installation including spikes

DIN-rail or screw-mount

& adjustment by

potentiometers

Easy installation

Littelfuse.com/t2100

Generator & single-Function Protection–excitation Loss

t2100 serIes

Excitation Loss Relay

Description

The T2100 Excitation Loss Relay protects against loss of

excitation in a synchronous generator. T2100 detects the

high-inductive current running into a generator in case of

low excitation. The faulty generator breaker is tripped, thus

protecting the generator, and avoiding undervoltage on the

busbar with a possible blackout of the system.
The T2100 calculates I x sin φ, representing the reactive

power. If the reactive power becomes negative and exceeds

the preset level (0.5-1.5 x I

N

), the pickup LED will indicate

and the delay timer will be started. After the preset time

(2-20 sec.) has expired, the output relay and LED will be

activated, provided that the negative reactive power level

was exceeded for the entire delay time.

Specifications

Trip Level

0.5-1.5 x I

N

Delay

2-20 sec.

Max. Voltage

660 V

Voltage Range

50-110%

Consumption

Voltage 5 VA at U

N

Current 0.3 VA at I

N

Continuous Current

2 x I

N

Frequency Range

45-400 Hz

Output Relay

Normally de-energized, latching, resetable

Contact Rating

AC: 400 V, 5 A, 1250 VA

DC: 150 V, 5 A, 120 W

Overall Accuracy

±5%

Repeatability

±1%

Operating Temperature –20°C to + 70°C

Dielectric Test

2500 V, 50 Hz

EMC

CE according to EN50081-1, EN50082-1,

EN50081-2, EN50082-2

Approvals

Certified by major marine classification societies

Burn-in

50 hours before final test

Enclosure Material

Polycarbonate. Flame retardant

Weight

0.5 kg

Dimensions H

70 mm (2.76”); W 100 mm (3.94”);

D 115 mm (4.52”)

Installation

35 mm DIN rail or 4 mm (

3

/

16

”) screws

OrderING

NumBer

termINaLs

I

N

suPPLy FuNctION

1-3

2-3

T2100.0010

230 V

5 A L-N

T2100.0020

480 V 415 V 5 A L-L

T2100.0030

450 V 400 V 5 A L-L

T2100.0040

110 V 100 V 1 A L-L

T2100.0050

110 V 100 V 5 A L-L

T2100.0060

110 V 100 V 5 A L-L

Current 0.2-1.2 x I

N

T2100.0070

480 V 415 V 5 A L-L

Normally energized output,

current 0.05 -0.15 x I

N

T2100.0080

110 V 100 V 5 A L-L

24 V DC aux. voltage

supply, current 0.2 1.2 x I

N

Ordering Information

Simplified Circuit Diagram

Features & Benefits

Other supply voltages and combinations are available on request.

Rev: 4-A-050213

Advertising