FPU-32 SerieS (PGr-7200)

Feeder Protection Unit

Description

The FPU-32 Feeder Protection Unit provides integrated

protection, metering, and data-logging functions. It is an excellent

choice for retrofitting and upgrading older relays because of its

compact size and ability to use existing CTs. The FPU-32 is

used to protect distribution feeders in processing, manufacturing,

petroleum, chemical, and wastewater treatment facilities.

MPU-CIM

(Current Input Module)

(Feeder Protection Unit)

(Feeder Protection Unit)

GF CT

L2

FPU-32

FPU-32

L1

PHASE CT

PHASE CT

CT

PHASE CT

1-A-SECONDARY PHASE CT’s

GF

L2

L1

NOTE: The FPU-32 consists of the Feeder Protection Unit (pictured above) and

the MPU-CIM Current Input Module (not pictured).

OrderinG nUmber

COmmUniCatiOnS

FPU-32-00-00

TIA-232

FPU-32-01-00

TIA-232 & RS-485

FPU-32-02-00

TIA-232 & DeviceNet™

FPU-32-04-00

TIA-232 & Ethernet

NOTE: One of the following is required: MPU-CIM-00-00 Current Input Module, or

MPU-CTI-RT-00 Current Input Module with ring-tonque terminals.

Ordering Information

Simplified Circuit Diagram

FeatUreS

beneFitS

IEC & IEEE overcurrent

protection curves

Definite and inverse time settings for system

coordination; prevents catastrophic failures

Two setpoint groups

Create distinctive settings for maintenance or for

two different loads

Reduced overcurrent

mode

Maintenance mode setting to reduce the risk of

arc-flash hazards

Data logging

On-board 100-event recorder and remote data

logging helps with system diagnostics

Overload

Thermal protection for connected load

Phase loss/Phase reverse

(current)

Detects unhealthy supply conditions

Unbalance (current)

Prevents overheating due to unbalanced phases

Communications

Remotely view measured values, event records

& reset trips

Features & Benefits

A

B

aCCeSSOrieS

reqUirement

Phase CTs

Recommended

Ground-Fault CT

Optional

MPU-16A-Y92A-96N

Optional

Specifications

Protective Functions
(IEEE Device Numbers)

Input Voltage

65-265 Vac, 30 VA; 80-275 Vdc, 25 W

Power-Up Time

800 ms at 120 vac

Ride-Through Time

100 ms minimum

24-Vdc Source

400 mA maximum

AC Measurements

True RMS and DFT, Peak 32 samples/cycle and

positive and negative sequence of fundamental

Frequency

50, 60 Hz

Output Contacts

Three Form C

Approvals

CSA certified, CE, C-Tick (

Australian

)

Communications

TIA-232 (standard); TIA-485, DeviceNet™, Ethernet (optional)

Analog Output

4-20 mA, programmable

Conformally Coated

Standard feature

Warranty

10 years

Mounting

(Control Unit)

Panel (standard)

Surface (with MPU-32-SMK converter kit)

(Current Input Module) DIN, Surface

Overload (49, 51)

Phase sequence (46)

Unbalance (46)

Phase loss (46)

Phase Current Transformers

Phase CTs are required to detect phase

currents.

Ground-Fault Transformer

Zero-sequence current transformer detects

ground-fault current. Available with 5-A and 30-A

primary ratings for low-level pickup.

B

Accessories

A

Definite-time overcurrent (50, 51)

Inverse-time overcurrent (50, 51)

Ground fault (50G/N, 51G/N)

RTD/PTC temperature (49)

Feeder Protection–Standard

Littelfuse.com/fpu-32

Rev: 4-A-050213

Based on Manual Rev 1