Littelfuse EL3100 Series User Manual

El3100 series, Protection relays & controls, Ground-fault & phase-voltage indicator description

Advertising
background image

Protection Relays & Controls

© 2013 Littelfuse Protection Relays & Controls

Ground-Fault Protection – Grounded/Ungrounded AC Systems

EL3100 SEriES

Ground-Fault & Phase-Voltage Indicator

Description

The EL3100 is a self-powered ground-fault and phase-

voltage indication system for 3-phase systems. The EL3100

meets the National Electrical Code (NEC) and the Canadian

Electrical Code (CEC) requirements for ground detectors

for ungrounded alternating-current systems. Voltage

connections are provided on the EL3100 for 208, 240, 480,

and 600-V systems. Three green LED’s on the EL3100

indicate the presence of phase-to-ground voltage and one

red LED indicates a ground fault. The EL3100 can operate

stand-alone or with up to five remote LED indicators. A

solid-state relay output provides indication of a ground fault.

The output relay is closed when the 3-phase neutral voltage

shifts as the result of ground leakage.

Specifications

Input Voltage

Input L: 208/240 Vac

Input H: 480/600 Vac

Dimensions

H 87.0 mm (3.43”)
W 112.5 mm (4.43”)
D 56.0 mm (2.2”)

Approvals

CSA certified, UL Listed (E340889)

Conformally Coated

Standard feature

Warranty

5 years

Mounting

DIN, Surface

OrdErinG nUmbEr

mOUnTinG

EL3100-00

DIN, Surface

Ordering Information

Simplified Circuit Diagram

FEATUrES

bEnEFiTS

NEC

®

and CEC Code

compliant

Meets National Electrical Code (NEC

®

) Article

250.21 and Canadian Electrical Code Part 1, Section

10-106 (2) requirements for ungrounded systems

Low-voltage

remote LEDs

System voltage is not present at the remote

LED location

Phase-voltage

indication

Indicates the presence of voltage on both

grounded and ungrounded systems

Output relay

Allows for remote ground-fault indication

Features & Benefits

(Ground-Fault &

Phase-Voltage

Indicator)

EL3100

Remote

LEDs

AH

G

AL

BH BL

CH CL

DN

DR

DG

DA

DB

DC

Output

Relay

A

B

C

Note: X=R for red LED and G for green LED

Y=0 for no label and 1 for a ground-fault label

Remote LEDs

High-intensity 16-mm IP67 LED lamps

available in red and green colors.

Accessories

A

A

ACCESSOriES

rEqUirEmEnT

RK-310x-0y

Optional

Rev: 4-B-050213

Based on Manual Rev 1

Littelfuse reserves the right to make product changes, without notice. Material in this document is as accurate as known at the time of publication. Visit Littelfuse.com for the most up-to-date information.

© 2013 Littelfuse Protection Relays & Controls

Littelfuse.com/EL3100

Advertising