Littelfuse BA_BB Varistor Series User Manual

Varistor products, Ba/bb varistor series

Advertising
background image

© 2013 Littelfuse, Inc.

151

Revised: May 8, 2013

Varistor Products

BA/BB Varistor Series

Industrial High Energy Terminal Varistors > BA/BB Series

Specifications are subject to change without notice.
Please refer to www.littelfuse.com/series/ba or /bb.html for current information.

HI–ENERGY

MO

V’S

BA/BB Series

BA/BB Varistor Series

Description

The BA and BB Series transient surge suppressors are
heavy-duty industrial Metal-Oxide Varistors (MOVs)
designed to provide surge protection for motor
controls and power supplies used in oil-drilling, mining,
transportation equipment and other heavy industrial AC line
applications.

These UL– recognized varistors have similar package
construction but differ in size and ratings. The BA models
are rated from 130 to 880V

M(AC)

. The BB models from 1100

to 2800V

M(AC)

.

Both the BA and BB Series feature improved creep and
strike capability to minimize breakdown along the package
surface, a package design that provides complete electrical
isolation of the disc subassembly, and rigid terminals to
ensure secure wire contacts.

See BA/BB Series Device Ratings and Specifications Table
for part number and brand information.

Features

• High energy absorption

capability W

TM

BA Series 3200J

BB Series 10,000J

Wide operating voltage
range V

M(AC)RMS

BA Series 130V to 880V

BB Series 1100V to 2800V

Rigid terminals for
secure wire contact

Case design provides
complete electrical
isolation of disc
subassembly

• Littelfuse

largest

packaged disc
60mm diameter

No derating up to
85ºC ambient

RoHS compliant

Agency Approvals

Absolute Maximum Ratings

• For ratings of individual members of a series, see Device Ratings and Specifications chart

Agency

Agency File Number

E320116 - for BA Series only.

CAUTION: Stresses above those listed in "Absolute Maximum Ratings" may cause permanent damage to the device. This is a stress only
rating and operation of the device at these or any other conditions above those indicated in the operational sections of this specification is
not implied.

Continuous

BA Series

BB Series

Units

Steady State Applied Voltage:

AC Voltage Range (V

M(AC)RMS

)

130 to 880

1100 to 2800

V

DC Voltage Range (V

M(DC)

)

175 to 1150

1400 to 3500

V

Transients:

Peak Pulse Current (I

TM

)

For 8/20μs Current Wave (See Figure 2)

50,000 to 70,000

70,000

A

Single Pulse Energy Range

For 2ms Current Squarewave (W

TM

)

450 to 3200

3800 to 10000

J

Operating Ambient Temperature Range (T

A

)

-55 to +85

-55 to +85

O

C

Storage Temperature Range (T

STG

)

-55 to +125

-55 to +125

O

C

Temperature Coefficient (a

V

) of Clamping Voltage (V

C

) at Specified Test Current

<0.01

<0.01

%/

O

C

Hi-Pot Encapsulation (COATING Isolation Voltage Capability)

(Dielectric must withstand indicated DC voltage for one minute per MIL–STD–202, Method 301)

5000

5000

V

COATING Insulation Resistance

1000

1000

RoHS

BB Series

BA Series

Advertising