Insulation Monitoring

T3200 SerIeS

Two-Channel Insulation-Monitoring Relay

Specifications

InsulationLevel

0-5 MΩ

Delay

1-10 sec.

Max. Voltage

660 V

Voltage Range

80-110%

Consumption

Max. 2 VA

Frequency Range

45-65Hz

Measuring Voltage

15 Vdc

Instrument Output

0-1 mA

Instrument Resistance Max. 100 Ω
Output relays

Normally de-energized; non-fail-safe

Contact Ratings

AC: 400 V, 2 A, 250 VA; DC: 110 V, 2 A, 100 W

Overall Accuracy

±5% of preset value

Operating Temperature –20°C to + 70°C
EMC

CE according to EN50081-1, EN50082-1,

EN50081-2, EN50082-2

Approvals

Certified by major marine classification societies

Enclosure Material

Polycarbonate. Flame retardant

Weight

0.5 kg

Dimensions H

70 mm (2.75”); W 100 mm (3.94”); D 115 mm (4.52”)

Installation

35 mm DIN rail or 4 mm (

3

/

16

”) screws

OrderIng nuMber

1-3 TerMInalS

2-3 TerMInalS

T3200.0010

230 V

T3200.0020

450 V

400 V

T3200.0030

480 V

415 V

T3200.0050

110 V

100 V

T3200.0060

127 V

120 V

Ordering Information

Simplified Circuit Diagram

Other voltages are available on request.

E2323 Megaohmmeter

Flush mounted units designed for connection

with the T3200 for instrument readings.

Features & Benefits

Accessories

A

acceSSOrIeS

dIMenSIOn

E2323.0010 Megaohmmeter

96 x 96 mm

E2333.0010 Megaohmmeter

144 x144 mm

Littelfuse.com/t3200

SYS. 1

COM

INS. 1

INS. 2

SYS. 1

SYS. 2

SYS. 2

5

+

6
7

13
15
11

1
2
3

18

19
20

8
9

10

L

1

L

2

L

3

T3200

(Double Insulation

Monitoring Relay)

E2323
(Megaohmmeter)

FeaTureS

beneFITS

Accepts high supply

voltage variation

Ensures correct operation in spite of voltage

supply fluctuations (fulfils marine class

requirement)

Visual indication of power,

pick-up, and output trip

Provides quick and concise status information

Direct line-line or line-

neutral voltage supply (up

to 690 Vac)

Simplifies design and installation.

No need for PTs.

Combined monitoring of

2 independent systems

Economic solution and occupying less space in

the switch panel

Available with separate

24 Vdc supply

Safe operation. Maintains protection regardless

of system voltage failure

Galvanic isolated inputs

Protects the unit against high AC voltage and

currents from the installation including spikes

DIN-rail or screw- mount

& adjustment by

potentiometers

Easy installation

A

Description

The T3200 Insulation-Monitoring Relay is designed for

continuous insulation monitoring on three-phase insulated

networks on board ships. The relay continuously monitors

two systems galvanically separated from each other, e.g.

the busbar and the lighting system, or two busbar systems.

The unit features two output relays for alarm purposes and

two analog outputs for instrument reading. Instruments are

available from Littelfuse Selco as standard-sized switchboard

instruments. The T3200 carries the CE label and has been

approved by major marine classification societies.