SE-145 SERIES

Ground-Fault Ground-Check Monitor

Description

The SE-145 is a three-channel, microprocessor-based,

combination ground-wire monitor and ground-fault relay for

resistance-grounded or solidly grounded systems. It continuously

monitors the integrity of the ground wire to protect portable

equipment from hazardous voltages caused by ground faults. The

SE-145 is designed for use on three-way splitter box applications.

Specifications

IEEE Device Numbers

Checking or Interlocking Relay (3GC),

Ground fault (50G/N, 51G/N)

Input Voltage

60-265 Vac, 60VA; 82-275 Vdc, 45W;

18-30Vdc, 45W

Dimensions

H 213 mm (8.4"); W 192 mm (7.6"); D 176 mm (7.0")

Trip Level Settings

0.5-12.5 A or 2.0-50.0 A

Trip Time Settings

0.1-2.5 s

Contact Operating Mode

Selectable fail-safe or non-fail-safe

Harmonic Filtering

Standard feature

Test Button

Standard feature

Reset Button

Standard feature

Communications Ethernet

Optional

Output Contacts

Isolated Form A and Form B

Conformally Coated

Standard feature

Warranty

5 years

Mounting

Panel, Surface

ORDERING NUMBER

CONTROL POWER

COMM

SE-145-00-00

120/240 Vac; 110-250 Vdc

SE-145-03-00

120/240 Vac; 110-250 Vdc

Modbus

®

TCP

SE-145-30-00

24 Vdc Battery Back-up

SE-145-33-00

24 Vdc Battery Back-up

Modbus

®

TCP

Ordering Information

See Current Transformer Selection Guide and Accessory Information.

SE-CS10 Series Ground-Fault Current

Transformer

Zero-sequence current transformer detects

ground-fault current. Provides 0.5 to 12.5 A

trip range.

SE-TA12A Series Termination Assembly

Required termination assembly; temperature

compensated.

Accessories

A

B

FEATURES

BENEFITS

Adjustable pickup

(0.5 - 12.5 A)

Unit can be used on a wide variety of trailing cable

applications

Adjustable time delay

(1 - 2.5 s)

Adjustable trip delay for quick protection and system

coordination

Output contacts

Separate annunciation of ground-fault and ground-

check faults

Ground-check

LED indication

Indication of open or short ground-check wire

makes it easier to find faults

CT-Loop monitoring

Alarms when CT is not connected

High-induced-ac

rejection

Makes unit suitable for applications with high

voltages and long cables

DFT (harmonic) filter

Prevents false operation

Zener-characteristic

termination assembly

Provides reliable ground-check loop verification

Fail-safe circuits

Ensures ground-check and ground-fault circuits

remain safe even in the event of equipment failure

Conformal coating

Additional coating protects circuit boards against

harsh environment

Features & Benefits

ACCESSORIES

REQUIREMENT

SE-CS10 or SE-CS40 Series

Required

SE-TA12A Series

Required

RK-132

Optional

Trailing Cable Protection–Ground-Fault Ground-Check Monitoring

SE-CS40 Series Ground-Fault Current

Transformer

Zero-sequence current transformer detects

ground-fault current. Provides 2.0 to 50 A

trip range.

C

TRAILING

CABLE

CHANNEL A

CHANNEL B

CHANNEL C

TRIP A

CT

L2

L1

TERMINATION

DEVICE

A

G

GC

C

B

GROUNDED

SUPPLY

M

SE-145

SERIES

(Ground-Fault

Ground-Check

Monitor)

B

A

Rev: 4-C-121013

Simplified Circuit Diagram

Application Diagram

L2

SE-135

L1

LOAD C

GC

G

SUBSTATION

GC

G

SE-145

GC A

G A

GC B

G B

GC C

G C

GC

G

SPLITTER
BOX

SE-TA12A

LOAD B

GC

G

SE-TA12A

LOAD A

GC

G

SE-TA12A

SE-TA12A

MODEM

COMM

TRIP A

TRIP B

TRIP C

C

C

C

C